Field
Description
Connection
Select the type of connection:
None
: If no device communicates with the console.
Serial
: If a serial RS232 connection is made between the POS/FCC and the console.
TCP/IP
: If a TCP-IP connection is made between the POS/FCC and the console.
Sales
Click
YES
if the POS/FCC will transmit the dispenser sales transactions to the console. The Gilbarco
BCD protocol is supported for this function. Note, that only one connection at a time can support the sales
transactions.
Protocol
Select one of the two
Gilbarco
: To permit the GVR TLS350 protocol commands.
DOMS OPC
: To permit the DOMS OPC protocol commands.
Port
If serial communication was selected above, select which serial port will be used (COM1 or COM2).
If TCP-IP communication was selected above, configure the TCP-IP port that to be used.
Baud rate /
Parity / Data
bits / Stop bits
Theses fields are in operation if serial communication has been selected. Configure the settings for the
serial ports.
Enable
Gilbarco Set
Commands
Select this button for a range of GVR TLS350 set commands to be used.
Printer
Connection
Select:
None
: If no printer is connected
USB
: If a printer is connected through the USB port.
COM1/COM2
: If a printer is connected to the serial port (baud rate for the printer should be set to
9600 bps). Note that this is necessary for the fields to become available if the serial ports have not been
configured for POS/FCC communication.
Click
Save
and
Apply settings to console
when you complete the
Protocols
tab configuration.
6.1.4 Tank Group
NOTE:
The number of tanks are configured in the Site Info tab. Tank parameters are
configured in Tanks setup from the Main Menu.
This tab is used to make Siphon (Manifold) groups.
IMPORTANT:
Tanks in a Siphon (Manifold) group must contain the same product.
M2051-EU Rev.: 1 Dover Fueling Solutions
Page 23