Allarmi / 

Alarms

Sia in funzionamento AUTOMATICO che MANUALE vi sarà un area del set-up adibita alla descrizione di eventuali allarmi presenti. Di seguito un elenco degli allarmi possibili
che il regolatore è in grado di segnalare:

Both in AUTOMATIC/MANUAL modes, there is an area of set-up used for description of any alarms. Below is a list of possible alarms that the controller is able to report:

NOME ALLARME

ALARM NAME

MESSAGGIO LCD

LCD MESSAGE

EVENTO ALLARME

ALARM EVENT 

POSSIBILE CAUSA

POSSIBLE CAUSE

A1

I CAP

Rilevata eccessiva corrente nei condensatori

D

etected excessive current in the capacitors (harmonic or Overvoltage)

armoniche o sovratensione

harmonics or overvoltage

A2

ERROR CAP

Rilevato errato valore batteria

Detected wrong value of battery 

Controllare funzionalità batterie

Check functionality batteries

 

A3

MAX V

Rilevata sovratensione nella tensione di picco istantanea ai condensatori

Overvoltage detected on the instantaneous peak voltage capacitors

Controllare rete elettrica

Check power grid

A3

ERROR VN

Rilevato tensione nominale diversa da quella impostata

Detected nominal voltage different from that set 

Controllare tensione di rete/frequenza

Check voltage grid and frequency

A4

MAX T

Rilevata temperatura eccessiva

Detected excessive temperature 

Controllare sonda/ventola o aerazione quadro

Check probe/fan or aeration panel 

A5

SYS TOO IND

Rilevato stato di stallo per impianto troppo induttivo

Detected stall state for plant too inductive 

Controllare funzionalità batterie

Check functionality batteries 

A5

SYS CAP

Rilevato stato di stallo per impianto capacitivo

Detected stall state for plant capacitive 

Controllare funzionalità teleruttori

Check functionality contactors 

Il comportamento del regolatore durante ognuno degli allarmi sopraelencati dipende dalle impostazioni scelte. Si può selezionare una delle 5 modalità di funzionamento per
ogni causa di allarme. Nella seguente tabella sono elencate tutte le possibili modalità di ciascun allarme:

The behavior of the controller during each of the alarms listed above depends on the settings chosen. You can select one of five modes of operation for any cause for alarm.
The following table lists all the possible modes of each alarm:

IMPOSTAZIONE ALLARME

A1-A2 … A5

ALARM SETTING 

A1-A2 … A5

FUNZIONAMENTO

RELE' ALLARME

FUNCTION OF 

 ALARM RELAY

LCD COLORE ROSSO

COLOR RED LCD

OFF

NO

NO

LCD

NO

SI

RLY

SI

NO

LCD-RLY

SI

SI

DIS (non possibile su A5)

DIS (not possible on A5)

SI + SGANCIO BATTERIE

YES + RELEASE BATTERIES

SI

MU 1219 R

EV

.2.01  13/03/15

Содержание RFX7

Страница 1: ... During set up you can manually set the value of each battery or start the Autosetting that it will obtain the values according to the value of reactive power measured the instrument is able to understand which batteries must be connected to restore the power factor cosφ above the threshold set by the user preferring the configurations allowed eligible with the fewest possible operations Precauzio...

Страница 2: ...ntroller will drive the last relay to start the ventilation giving clear visual indication by icon to the left of the temperature measurement The display is given clear indication of the batteries connected blacking out the box When a battery is disconnected the corresponding box flashes until the end of the discharge time after which the battery will again be available for new connections Under t...

Страница 3: ...e Autosetting procedure will not start or stop if there are not these above conditions in thIs case the message will appear on the display INST ERROR PAG pulsante per passare alla pagina di set up successiva PAG button to switch to the next setup page SET una pressione rapida per passare da un parametro a quello successivo riconoscibile perché lampeggiante Premere per 3 secondi per entrare uscire ...

Страница 4: ...ete frequenza Check voltage grid and frequency A4 MAX T Rilevata temperatura eccessiva Detected excessive temperature Controllare sonda ventola o aerazione quadro Check probe fan or aeration panel A5 SYS TOO IND Rilevato stato di stallo per impianto troppo induttivo Detected stall state for plant too inductive Controllare funzionalità batterie Check functionality batteries A5 SYS CAP Rilevato stat...

Отзывы: