background image

2

TS 97 FL XEA

2019-08

dormakaba Mounting instructions

Safety

WN 059870 45532

1

2

Position numbers of components

The icon indicates the installation 
stages of the supplied cable loop

The icon indicates installation stages if 
the supplied cable loop is not mounted.

The icon indicates installation stages 
when the door closer is mounted on the 
door leaf.

The icon indicates installation stages 
when the door closer is mounted on the 
door lintel.

1.6.1  Tool icons

Allen wrench,  
e.g. wrench size 3

2  Safety

2.1  Intended use

The TS 97 FL XEA is intended solely for the controlled 
closing of swing doors with the following properties:
•  Maximum door leaf weight 180 kg
•  Maximum door leaf weight 1,400 kg
•  Maximum door opening angle approx. 145° when 

TS 97 FL XEA is mounted on the door leaf on the 
hinge side, on the lintel on the hinge side, or on the 
lintel on the opposite side to the hinge.

•  Maximum door opening angle approx. 105° when 

TS 97 FL XEA is mounted on the door leaf on the 
opposite side to the hinge.

•  The swing door’s opening angle must be limited by a 

doorstop.

•  An external manual release button is required to 

interrupt the power supply. The manual release 
button must not be covered by the opened door.

Observe country-specific regulations when using on 
fire barriers, fire protection doors and smoke barriers. 
Do not operate the TS 97 FL XEA on the lintel on the 
opposite side to the hinge for fire protection doors.

2.2  Prerequisites for the operation of hold-

open systems

The use of hold-open systems is subject to special 
provisions due to the official approval regulations. 
These provisions relate in particular to acceptance, 
ongoing monitoring and maintenance. Observe the 
instructions in the information sheet on the use of 
hold-open systems. Additional requirements apply for 
use as fire/smoke protection closure in conjunction 
with external RMZ and RM. A separate verification 
of suitability is required for the respective fire/smoke 
protection door.

2.3  Requirements for the electrical 

installation by the customer

Before mounting, connect the cables to the TS 97 FL 
XEA’s 24 V DC power supply. Only use the cable loop 
supplied when mounting the TS 97 FL XEA on the door 
leaf’s hinge side. 

3  Product description 

The TS 97 FL XEA is a slide rail door closer with 
freewheel function. The door closes automatically in 
the following cases: 
•  In case of power failure
•  In connection with an external RMZ in case of fire
•  In conjunction with an external manual switch

7° - 0°

145° - 0°

3

4

6

5

1

2

Fig. 1 

TS 97 FL XEA in DIN-L mounting on the door leaf

(1) 

Slide rail (without cladding)

(2) 

Lever arm

(3) 

TS 97 FL XEA (without cladding)

(4) 

Adjusting screw for adjusting the closing force 

(5) 

Valve for adjusting the closing speed

(6) 

Valve for adjusting the end stop

3.1  Technical data

Supply voltage operating 
voltage
Power consumption

24 V DC +/- 15 % 
approx. 3 W

Ambient temperature:

-15°C to +40°C

Rel. humidity:

up to 93%  
(non condensing)

Protection class:

IP 54

Содержание TS 97 FL XEA

Страница 1: ...life of the product and must be passed on with the product 1 5 Safety instructions CAUTION This signal word indicates a situation of potential risk which could lead to minor or slight injury if not averted 1 6 Symbols used 1 2 Step by step graphics dormakaba Deutschland GmbH Postfach 4009 58256 Ennepetal 19 0432 CPR 00026 58 EN 1154 1996 A1 2002 AC 2006 EN 1155 1997 A1 2002 AC 2006 3 8 3 6 1 1 4 D...

Страница 2: ...e opposite side to the hinge for fire protection doors 2 2 Prerequisites for the operation of hold open systems The use of hold open systems is subject to special provisions due to the official approval regulations These provisions relate in particular to acceptance ongoing monitoring and maintenance Observe the instructions in the information sheet on the use of hold open systems Additional requi...

Страница 3: ...is loosened during repair or maintenance work the screw must be replaced by a new self locking original screw Mount the lever arm according to the illustrated instructions and the mounting variant 4 4 Adjust door closer 9 Adjust the door closer power 10 1 Adjust the closing speed 2 Adjust the end stop 4 5 Mount the cladding 11 13 Carry out the mounting according to the enclosed illustrated instruc...

Страница 4: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com Translation of the original manual subject to change without notice ...

Отзывы: