4.8 Set the sequential locking
control
Only if the clamp plate is adjusted correctly, can the
active leaf be moved into the direction of closing
properly while the fixed leaf is closed.
The clamp plate is adjusted correctly when the
connecting tube pushes the clamp plate into a
rectangular position via the adjusting sleeve.
Carrying out the setting as follows:
1.
Close the fixed leaf.
2.
Close the active leaf.
3.
Unscrew the adjusting sleeve manually so far that
the pin
2 drops out. In the process, the clamp
plate must be in a rectangular position to the
clamping rod 1 . The pin holds the sequential
locking control in a neutral position without
hindering and will not be required after mounting.
4.
Secure the adjusting sleeve with the plastic bolt.
4.9 Check the sequential locking
control
WARNING
Risk of smoke inhalation
If the GSR‑EMF XEA BG is used as fire and
smoke protection closure the sequential
locking control must work perfectly. If the
sequential locking of the door leaves is not
achieved the catching device must not be
used on fire and smoke protection doors.
• Mount a catch cap.
1.
Open of the active leaf.
2.
Open of the fixed leaf.
3.
Hold the fixed leaf.
4.
Change the position of the active leaf to the
opening direction. The active leaf must be set in
each position.
5.
Let the fixed leaf close. The active leaf must only
close automatically when the fixed leaf is closed.
If the triggering roller is not swiveled by the trigger,
the trigger must be moved.
1.
Close the fixed leaf.
2.
Loosen the screw.
3.
Push the trigger into the direction of the
triggering roller.
4.
Tighten the screw
4.10 Connect the EMF
Only for GSR‑EMF XEA
1.
Lay the EMF‑connecting cables of the fixed leaf
to the active leaf in a way that it is not resulting
in jamming the connecting rod.
2.
Tighten the cable with zip ties.
3.
Insert the connection cable of the EMF fixed leaf
into the EMF active leaf.
4.
Insert the 24/48‑V‑DC connecting cable of the
RMZ or of the fire detection system by customers
into the EMF active leaf.
5 Start up
Only for GSR‑EMF XEA
5.1 Set the fixture point
ATTENTION
Risk of cable damage
While setting the fixture points cables might
be damaged.
• Pay attention not to jam the connecting
cables.
1.
Feed the power supply (24 V/48 V DC).
2.
Open the fixed leaf until it clicks.
3.
Unbolt the screws of the locking unit(s).
4.
Open the door leaves to the desired opening
angle.
5.
Tighten the screws of the locking unit(s) again.
6.
Place the door stop into the position of the fixture
points selected.
5.2 Set the release force
ATTENTION
Risk of damaging the slide rail system
Setting a release force too high may result
in damage to the door hinges and the
fastening elements of the door closing
system.
• Set the release force depending on the
door width and the selected size of the
closing contact.
• According to the DIN EN 1155 the release
force must not be less than 40 Nm at a
door opening angle of 90 and not more
than 120 Nm.
1.
Set the release force.
2.
Control the release force.
5
GSR XEA BG/GSR-EMF XEA BG
2017-10
dormakaba Mounting instructions
WN 059385 45532
Start up