Dormakaba GSR XEA BG Скачать руководство пользователя страница 5

4.8  Set the sequential locking 

control

Only if the clamp plate is adjusted correctly, can the 
active leaf be moved into the direction of closing 
properly while the fixed leaf is closed.
The clamp plate is adjusted correctly when the 
connecting tube pushes the clamp plate into a 
rectangular position via the adjusting sleeve. 
Carrying out the setting as follows:

1. 

Close the fixed leaf.

2. 

Close the active leaf.

3. 

Unscrew the adjusting sleeve manually so far that 
the pin 

 

2  drops out. In the process, the clamp 

plate must be in a rectangular position to the 
clamping rod  1 . The pin holds the sequential 
locking control in a neutral position without 
hindering and will not be required after mounting.

4. 

Secure the adjusting sleeve with the plastic bolt.

4.9  Check the sequential locking 

control

WARNING

Risk of smoke inhalation

If the GSR‑EMF XEA BG is used as fire and 
smoke protection closure the sequential 
locking control must work perfectly. If the 
sequential locking of the door leaves is not 
achieved the catching device must not be 
used on fire and smoke protection doors.
•  Mount a catch cap.

1. 

Open of the active leaf. 

2. 

Open of the fixed leaf.

3. 

Hold the fixed leaf.

4. 

Change the position of the active leaf to the 
opening direction. The active leaf must be set in 
each position.

5. 

Let the fixed leaf close. The active leaf must only 
close automatically when the fixed leaf is closed. 

If the triggering roller is not  swiveled by the trigger, 
the trigger must be moved.

1. 

Close the fixed leaf.

2. 

Loosen the screw.

3. 

Push the trigger into the direction of the 
triggering roller.

4. 

Tighten the screw

4.10  Connect the EMF 

Only for GSR‑EMF XEA

1. 

Lay the EMF‑connecting cables of the fixed leaf 
to the active leaf in a way that it is not resulting 
in jamming the connecting rod.

2. 

Tighten the cable with zip ties.

3. 

Insert the connection cable of the EMF fixed leaf 
into the EMF active leaf.

4. 

Insert the 24/48‑V‑DC connecting cable of the 
RMZ or of the fire detection system by customers 
into the EMF active leaf.

5  Start up

Only for GSR‑EMF XEA

5.1  Set the fixture point

ATTENTION

Risk of cable damage

While setting the fixture points cables might 
be damaged.
•  Pay attention not to jam the connecting 

cables.

1. 

Feed the power supply (24 V/48 V DC).

2. 

Open the fixed leaf until it clicks.

3. 

Unbolt the screws of the locking unit(s).

4. 

Open the door leaves to the desired opening 
angle.

5. 

Tighten the screws of the locking unit(s) again.

6. 

Place the door stop into the position of the fixture 
points selected.

5.2  Set the release force

ATTENTION

Risk of damaging the slide rail system

Setting a release force too high may result 
in damage to the door hinges and the 
fastening elements of the door closing 
system. 
•  Set the release force depending on the 

door width and the selected size of the 
closing contact. 

•  According to the DIN EN 1155 the release 

force must not be less than 40 Nm at a 
door opening angle of 90 and not more 
than 120 Nm.

1. 

Set the release force.

2. 

Control the release force.

5

GSR XEA BG/GSR-EMF XEA BG

2017-10

dormakaba Mounting instructions

WN 059385 45532

Start up

Содержание GSR XEA BG

Страница 1: ...il 4 4 4 Mount the door closer 4 4 5 Shorten the connecting tube 4 4 6 Adjust the triggering roller on the door leaf 4 4 7 Mount the connecting tube 4 4 8 Set the sequential locking control 5 4 9 Check the sequential locking control 5 4 10 Connect the EMF 5 5 Start up 5 5 1 Set the fixture point 5 5 2 Set the release force 5 5 3 Mount the paneling 6 5 4 Check the EMF 6 5 4 1 Release EMF manually 6...

Страница 2: ... is authorized by dormakaba The operating of the slide rail system can be carried out by any person who is mentally and physically able 1 3 Provided documents Mounting instructions Additionally with GSR EMF XEA BG Data sheet about the use of catching devices 1 4 Symbols and abbreviations used 1 4 1 Safety instructions WARNING This statement indicates a situation of potential risk which could lead ...

Страница 3: ... for the use as fire and smoke protection closures in conjunction with the external RMZ and RM A separate verification of suitability is required for the respective fire smoke protection door 3 Product description The slide rail system ensures the correct order when closing 2 winged doors The slide rail system is intended for the mounting into the opposite hinge side The slide rail system is suita...

Страница 4: ...Insert the end caps connector into the slide rail 2 A Tighten the slide rail B Tighten the slide rail on the pre installed mounting plate C Tighten the slide rail on the pre installed lintel casing angle 4 4 Mount the door closer ATTENTION Risk of damaging the slide rail system The dimensions on the drill template of the door closer are not suitable for the mounting of this product Use the dimensi...

Страница 5: ... trigger the trigger must be moved 1 Close the fixed leaf 2 Loosen the screw 3 Push the trigger into the direction of the triggering roller 4 Tighten the screw 4 10 Connect the EMF Only for GSR EMF XEA 1 Lay the EMF connecting cables of the fixed leaf to the active leaf in a way that it is not resulting in jamming the connecting rod 2 Tighten the cable with zip ties 3 Insert the connection cable o...

Страница 6: ...ease of the RMZ etc The door leaves are released and close The active leaf closes only when the fixed leaf is closed 6 Operating Only for GSR EMF XEA 6 1 Open and lock door 1 Open door leaves to the fixture point The door leaves remain standing after letting go 6 2 Close door 1 Firstly press shut the fixed leaf then the active leaf against the resistance or press the optional manual release button...

Страница 7: ...7 GSR XEA BG GSR EMF XEA BG 2017 10 dormakaba Mounting instructions WN 059385 45532 ...

Страница 8: ...dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com Translation of the original manual subject to change without notice ...

Отзывы: