background image

DORMA

DORMA

RMZ

Installation arrangement of the RMZ lintel-mounted

smoke detector for applications where the bottom

surface of the ceiling is less than 1 m above the

bottom edge of the lintel on one or both sides of the

door. 

1)

1)

1)

1)

1)

See separate sheet for associated connection

diagrams.

If the bottom surface of the ceiling is more than 1 m

above the bottom edge of the lintel on one or both

sides of the door, two ceiling-mounted smoke

detectors must be installed in addition to the lintel-

mounted detector. 

1)

1)

1)

1)

1)

See separate sheet for associated connection

diagrams.

The RMZ lintel-mounted smoke detector is installed

directly above the door opening (min. 10 mm).  The

vertical distance above the bottom edge of the lintel/

transom must not be more than max. 0.1 m.

Mark and drill the fixing holes and the necessary

cable lead-throughs for the 230 V power lead, hold-

open device, ceiling-mounted detectors and manual

pushbutton in accordance with the drilling template.

Install the necessary cabling.

In order to comply with protection class II     (total

insulation), the 230 V power lead should be installed

with double insulation up to the connection terminal.

Remove cable insulation at the end.

Break out the cable lead-through.

Fit end caps and fix the RMZ smoke detector.

Terminal assignment

Connect hold-open device(s) to terminals.

Connect any ceiling-mounted detectors and/or

manual pushbuttons – see connection diagrams.

Terminal resistors must be properly installed!

Insert and connect smoke alarm module (option).

The alarm module cannot be used if relay contacts 7,

8 and 9 are already in use.

Connect the power supply cable. Close the shock

hazard protection cover and screw down.

FIXING INSTRUCTIONS

Technical Data RMZ

Input:

230 V AC +10%/-15%

120 mA/28 VA / 50 Hz

Output:

24 V DC /460 mA / 11 W

Type of protection:

IP 30

Protection class:

II

Smoke switch:

24 V DC/50 mA

Temperature:

-20°C/+60°C

• Work on electrical equipment and systems may

only be performed by properly trained specialist
personnel.

• Check to ensure that the line power supply (230 V

AC) has been disconnected and is no longer live.

• 10 A/Bminiature circuit breaker must be provided

in the supply circuit. This can also be used as the
isolator for disconnecting the RMZ and making it
dead.

• The power cable leading to the RMZ must be

properly secured to ensure effective strain relief.

• he power cable (NYM) conductor cross section should

not be greater than max. 1.5 mm

2

.  The PE

conductor is not electrically utilised.  The terminal
(PE) should, however, be used where a PE conductor
is provided.

• The RMZ smoke detector should only be installed

as a lintel-mounted unit, and should only be
commissioned once firmly fixed to the wall.

• Fire/smoke detectors controlling hold-open

systems must not be used to actuate any further
alarm devices (e.g. fire alarm transmission
systems). 

1)

• If the optional alarm module is installed, the cable

connecting it to the smoke switch must be led over
and across the measurement chamber in order to
ensure that smoke penetration is in no way
hindered.

RMZ smoke detector

Electro-magnetic hold-open device

RM smoke detector

DORMA HT manual release pushbutton for hold-

open devices – mandatory for hold-open electro-

magnets and free-swing door closers;  otherwise

optional.

This pushbutton must not be concealed by the

door when in its hold-open position. 

1)

1)

1)

1)

1)

1 )

1 )

1 )

1 )

1 )

Guidelines for hold-open systems issued by the Institute for Building Technology,
Berlin.  In countries outside Germany, consult local regulations.

a

b

1

2

3

4

WN 056817  45532

   09/08