Installation
24
Instruction Manual DR-FC
3
is
3.6
Water connections,
Unvented
3.6.1
Cold water side
.
1. Fit an approved stop valve
on the cold water side as required by
regulations.
Refer also to paragraph
’1.3 Regulations and documents’
.
2. The maximum working pressure of the water heater is 8 bar. Because the
pressure in the water pipe at times can exceed 8 bar, you must fit an
approved pressure-reducing valve
.
3. Fit a non-return valve
and an expansion vessel
.
4. Fit an expansion valve
and connect the discharge to a drain via a tundish.
3.6.2
Top to bottom recirculating pump
You can connect a top to bottom recirculation pump to prevent stratification of
the water ("stacking")in the water heater.
1. Fit a pipe (Ø 22 mm), a stop valve
and a top to bottom recirculation
pump
.
2. Fit non-return valve
3. Fit stop valves
3.6.3
Hot water side
.
n
Remark
Insulating long hot water pipes prevents unnecessary energy loss.
1. Optional: fit a temperature gauge
to be able to check the temperature of
the tap water.
.
in the hot water outlet pipe, for use when servicing.
3.6.4
Circulation pipe
.
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump
of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valve
a downstream the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves
4. Connect the circulation pipe to the cold water supply pipe.
3.6.5
Condensation drainage
1. Fit a sloping wastewater pipe to the siphon
for condensation drainage and
connect this to the wastewater discharge in the boiler room.
c
Note
All piping behind the siphon must be condensation-resistant.
Содержание DR-FC 25
Страница 2: ...2...
Страница 6: ...6 Instruction Manual DR FC gis A Appendices 95 A 1 Introduction 95 A 2 Electrical diagram DR FC 96...
Страница 16: ...Functioning of the water heater 16 Instruction Manual DR FC 2 gis...
Страница 42: ...Filling and draining 42 Instruction Manual DR FC 4 gis...
Страница 46: ...The control panel 46 Instruction Manual DR FC 5 gis...
Страница 50: ...Status of the water heater 50 Instruction Manual DR FC 6 gis...
Страница 56: ...Starting up and shutting down 56 Instruction Manual DR FC 7 gis...
Страница 68: ...Main menu 68 Instruction Manual DR FC 8 gis...
Страница 72: ...Service program 72 Instruction Manual DR FC 9 is...
Страница 88: ...Troubleshooting 88 Instruction Manual DR FC 10 gis...
Страница 90: ...Maintenance frequency 90 Instruction Manual DR FC 11 gs...
Страница 98: ...Appendices 98 Instruction Manual DR FC A is...