Installation
18
Instruction Manual DR-FC
3
is
3.3.1
Humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost.
shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the water heater to be guaranteed.
3.3.2
Maximum floor loading
In connection with the water heater’s weight, take account of the maximum floor
loading, see
3.3.3
Working clearances
For access to the water heater it is recommended that the following
clearances are observed (see
•
AA: around the water heater’s control column and cleaning openings: 100
cm.
•
BB: around the water heater itself: 50 cm.
•
Above the water heater (room to replace the anodes):
-
100 cm if using fixed anodes, or
-
50 cm if using flexible anodes.
Table 3.1
Humidity and ambient temperature specifications
Humidity and
ambient
temperature
Humidity
max. 93% RH at +25°C
Ambient temperature
Functional: 0
≤
t
≤
60°C
Table 3.2
Weight specifications related to maximum floor loading
Weight of the water heater filled with water
DR-FC 25
402 kg
DR-FC 30, DR-FC 45, DR-
FC 60
606 kg
Содержание DR-FC 25
Страница 2: ...2...
Страница 6: ...6 Instruction Manual DR FC gis A Appendices 95 A 1 Introduction 95 A 2 Electrical diagram DR FC 96...
Страница 16: ...Functioning of the water heater 16 Instruction Manual DR FC 2 gis...
Страница 42: ...Filling and draining 42 Instruction Manual DR FC 4 gis...
Страница 46: ...The control panel 46 Instruction Manual DR FC 5 gis...
Страница 50: ...Status of the water heater 50 Instruction Manual DR FC 6 gis...
Страница 56: ...Starting up and shutting down 56 Instruction Manual DR FC 7 gis...
Страница 68: ...Main menu 68 Instruction Manual DR FC 8 gis...
Страница 72: ...Service program 72 Instruction Manual DR FC 9 is...
Страница 88: ...Troubleshooting 88 Instruction Manual DR FC 10 gis...
Страница 90: ...Maintenance frequency 90 Instruction Manual DR FC 11 gs...
Страница 98: ...Appendices 98 Instruction Manual DR FC A is...