Wiegand Keypad / Card Reader 

 

These instructions apply to the following DoorKing Products:  1815-247, 1815-248, 1815-249, 1815-250 with circuit 

board P/N 1515-009.    
When used to control entry through an automated vehicular gate system, the keypad / card reader must be 

mounted a minimum of 10-feet away from the gate and gate operator, or mounted in such a way that the 

person using the keypad cannot come into contact with the gate or gate operator. 
Both the keypad and card reader output their data in a 26-bit wiegand format and must be connected to an access 

controller such as the DKS models 1833, 1835, 1837 or 1838.  Each device operates independently of each other. 
 
 
 

Orange

Gray

Re

d

Bl

a

ck

G

reen

Wh

it

e

1  Common (Black)
2  Power (Red)
3  Earth Ground
4  Wiegand Common
5  Not Used
6  Data 0 (Green)
7  Data 1 (White)
8  Not Used

Gray  

12-24 Volt AC or DC

Orange

12-24 Volt AC or DC

Green

Data 0

White

Data 1

Black

Common

Red

Power

Power for LED Lights

To Access Controller

Keypad OR Card opens door/gate

Connect the keypad terminals to the card reader terminals (Red, 
Black, Green, White) and then connect to access controller.

Keypad AND Card opens door/gate

Each device must have separate weigand wire runs to the 
controller with each device operating a different controller relay.  
Relay contacts are wired in series to device to be controlled.  
Suggest setting relay strike times to 5 sec.

Keypad / Card opens different doors/gates

Each device must have separate weigand wire runs to the 
controller with each device operating a different controller relay.  
Relay contacts are wired to individual devices to be controlled.

1 2 3 4 5 6 7 8

Black

Red

White

Green

M

as
ter

 C

o

de

 

 