7
FIG. 8
THERMOCOUPLE
SCREW
RETAINER
THERMOCOUPLE
CONNECTION
BURNER
JET
TEST
PORT
CLEAR BLUE COLOR
OF FLAME
FIG. 9
REFRIGERATORS WITH AUTOMATIC REIGNITORS
(RM2552 & RM2553)
A. Start the refrigerator according to the instructions for
Gas Operation with Automatic Reignitor. See
Section
B. Operating Instructions, Item 3, Gas Operation.
B. Check that the gas flame is lit by observing flame
indicator (E). (See FIG. 9).
C. Close the gas valve by turning the knob "A" back to the
"OFF" position. (See FIG. 9)
D. Wait one minute, then disconnect the 12 volt DC power.
(See FIG. 6 and 6A).
E. Remove burner cover plate. (See FIG. 6 and 6A). Open
the gas valve by turning knob "A" to the "GAS" position
without pushing button "C". (See FIG. 9). The reignitor
should not be sparking. Apply commercial leak-check
bubble solution to the burner jet. (See FIG. 8). Be
careful not to damage burner jet.
F. No bubbles should appear at the opening of the burner
jet. Bubbles indicate a defective gas safety shutoff and
service is required.
G. If no bubbles were present at the burner jet, rinse the
orifice with water. Replace the burner cover plate.
Reconnect the 12 volt DC power supply to the refrigera-
tor. See Section A. Installation, Item 11, 12 Volt DC
Connection. Start the refrigerator by following the in-
structions for gas operation with automatic reignitor.
Normal gas operation should now return. Allow the
burner to operate a minimum of five minutes.
! WARNING
DO NOT use a flame to check for leaks.
FIG. 10
10. 120 VOLT AC CONNECTION
The refrigerator is equipped with a three-prong (grounded)
plug for protection against shock hazards and should be
plugged directly into a properly grounded three-prong
receptacle. DO NOT cut off or remove the grounding prong
from this plug. The free length of the cord is 2 feet and
therefore recommended that the receptacle be located to
the left side of the refrigerator (viewed from the rear) and
approximately 6 inches from the floor. (See FIG. 10). This
allows easy accessibility through the vent door. The cord
should be routed to avoid contacting the burner cover, flue
cover, or any other components that could damage the
cord insulation.