Dometic 39626.501 Скачать руководство пользователя страница 1

1

INSTALLATION INSTRUCTIONS

APPLICATION MANUAL

AND

INSTALLATION INSTRUCTIONS

THIS UNIT IS DESIGNED FOR OEM INSTALLATION

ALL INITIAL INSTALLATIONS MUST BE APPROVED BY THE SALES DEPT.

ROTARY COMPRESSOR

SYSTEM MODELS

Air Conditioners

39626.501 & 39626.506

Heat Pumps

39726.501 & 39726.506

SYSTEM

MODELS

SELF-CONTAINED

AIR CONDITIONER & HEAT PUMP

FOR

RECREATIONAL VEHICLES

REVISION:
Form No. 

3308463.011 

 5/06

(Replaces 3308463.003
(French 3308477.011)
©2003 Dometic Corporation
LaGrange, IN  46761

WARNING

!

This manual must be read and un-
derstood before installation, adjust-
ment, service, or maintenance is
performed. This unit must be in-
stalled by a qualified service techni-
cian. Modification of this product
can be extremely hazardous and
could result in personal injury or
property damage

39626.501
39626.506

39726.501
39726.506

US

Important:

 Instructions must stay with unit.

Owner read carefully

RECORD THIS INFORMATION FOR FUTURE REFERENCE
BEFORE INSTALLING THE UNIT:

Model Number
Serial Number
Date Purchased
Place of Purchase

Lire et comprendre ce manuel avant de
procéder à l'installation, à des réglages,
de l'entretien ou des réparations.
L'installation de cet appareil doit être
effectuée par un réparateur qualifié.
Toute modification de cet appareil peut
être extrêmement dangereuse et
entraîner des blessures ou dommages
matériels.

AVERTISSEMENT

!

USA
SERVICE OFFICE
Dometic Corporation
2320 Industrial Parkway
Elkhart, IN 46516
574-294-2511

CANADA
Dometic Corporation
46 Zatonski, Unit 3
Brantford, ON N3T 5L8
CANADA
519-720-9578

For Service Center
Assistance Call:
800-544-4881

Содержание 39626.501

Страница 1: ...of this product can be extremely hazardous and could result in personal injury or property damage 39626 501 39626 506 39726 501 39726 506 US Important Instructionsmuststaywithunit Owner read carefull...

Страница 2: ...2 4 HIGH POT REQUIREMENTS PAGE 8 2 5 MOUNTING IN COACH PAGE 9 2 6 WIRING DIAGRAM 39726 501 39726 506 PAGE 10 2 7 SPECIFICATIONS HEAT PUMP PAGE 10 2 8 WIRING DIAGRAM 39626 501 39626 506 PAGE 11 2 9 SPE...

Страница 3: ...ructions UNDERSTAND SIGNAL WORDS Asignal word WARNING OR CAUTION is used with the safety alert symbol They give the level of risk for potential injury indicates a potentially hazard ous situation whic...

Страница 4: ...illdirecttheairtothesources of the greatest heat loss and or heat gain The effects of the gain or loss can then be offset by the supply air It is important that the selection of the diffusers and gril...

Страница 5: ...the smallest size duct that will do the job of delivering required airflow rate with pressure available Nosinglesizeofductwillprovetobeidealfor all jobs B Length of Duct Pressure loss increases as du...

Страница 6: ...es R W D R W RR Radius Ratio RR or RR 1 5 FIG 2 4 PREFERRED Standard FAIR POOR NOT ACCEPTABLE Various Elbows Showing Radius Ratios FIG 2 3 R b R a D W CR R a R b Curve Ration CR Optimum Reading CR 05...

Страница 7: ...orizontally projected air streams The air stream from the outlet tends to hug the surface As a matter of fact this characteristic is almost essential for goodcomfortairconditioning Therefore rathertha...

Страница 8: ...ct Area Requirement See Figure 2 10 3 Return air to the system must be filtered to prevent dirtaccumulationontheevaporatorcoolingsurface 4 Returnairopeningmustbewithinminimumsspeci fied in the system...

Страница 9: ...nd reg ister location so that you receive maximum performance from the system These instructions DO NOT cover or warrant the final installation of the duct work that carries conditioned air within the...

Страница 10: ...s When sizing the generator the total electrical power must be taken into consideration Keep in mind that generators lose power because of altitude increases above sea level high outdoor temperatures...

Страница 11: ...acity 26 000 Volts Phase Hertz each circuit 115 AC 1 60 Run Amps Comp Circuit 1 10 1 Circuit 2 9 8 LRA Compressor Circuit 1 59 0 Circuit 2 59 0 Total Blwr Fan Motor Run Amps 8 5 Circuit 1 Total Blwr F...

Страница 12: ...structions carefully before attempting to start your unit installation B Dometic Corporation will not be liable for any damages or injury incurred due to failure in the following of these instructions...

Страница 13: ...aw through type When the faceofthecoilispositionedbehindalouveredorother type of restrictive opening the FREE AREA of the opening must be at least 648 square inches FIG 3 3 8 8 2 2 2 1 2 1 2 1 2 1 2 3...

Страница 14: ...olators should be used at each mounting point 12 VDC required for thermostat operation INSULATED DUCT Minimum Maximum 45 IN 2 80 IN 2 3 depth Min FIG 3 4 Supply Duct must be insulated Supply Duct from...

Страница 15: ...ng area is normally a good location Note If the system is to be used with a Remote Temperature Sensor the Comfort Control Center may be mounted anywhere that is convenient in the coach 8 Try to avoid...

Страница 16: ...differential between the first and second stage is preset and cannot be changed E Turn ON the furnace dip switch when a furnace is connected to the blue wires off the control board F Differential dip...

Отзывы: