background image

 

domat UC905 

08/2018 Subject to technical changes. 

1

 

 

 

 

UC905 

Room unit for controller FCR015 

 

 

 

 

 

Summary 

The  UC905  room  unit  is  a  communicative  human-machine  interface  for  VAV  unit 
controller FCR015. 
 
According to production type, each version of the unit may contain display, backlight  
and knob. 
 

UC0905 

 basic version with display and knob 

UC905BL 

 version with display, knob and backlight 

UC905DK 

 version without knob and display 

 
The  UC905  is  successor  of  UC095  room  unit  and  can  be  used  with  controllers 
FC015  and  FCR015.  Beware  of  unit  terminals  connection.  It  differs  from  its 
predecessor. 

 

Application 

 

VAV systems 

 measurement and control of room temperature and CO

2

 

concentration. 

Function 

The  unit  reads  room  temperature,  humidity  and  CO

2

  concetration  in  the  room  air, 

temperature correction / setpoint by a knob, and required operation mode which is set 
by a short push or in the menu. Data is transmitted to the room controller. The main 
controller, FCR015, may send to the unit other data (heating / cooling mode, fan stage, 
day / night / standby mode etc.) which are displayed on the LCD display.  
 
Connect the room unit to FCR015 over a 4 core cable, the most suitable types are JY(St)Y 
or LAM 2x2x0.8. Use the same type which powers the FCR015 controller as if the room 
unit power is taken from the FCR015 terminals, the cores in a terminal should be of the 
same cross-section. 
If there is communication failure between UC905 and FCR015, there is a wrench and 
alarm  bell  icon  at  the  UC905  display.  Check  signal  polarity  (terminals  8,  9),  bus 
termination, and correct wiring at the FCR015 side (see FCR015 data sheet). 
 

Technical data 

Power supply 

24 V AC +/- 20% 

Consumption 

3 W 

Galvanic isolation 

1 kV 

Содержание UC905

Страница 1: ...oncetration in the room air temperature correction setpoint by a knob and required operation mode which is set by a short push or in the menu Data is transmitted to the room controller The main controller FCR015 may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FCR015 over a 4 core cable the mos...

Страница 2: ...nsions 90x115x30 mm Ambient temperature External conditions 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 3 climatic class 3K5 Storage 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 1 climatic class 1K3 Standards conformity EMC EN 61000 6 2 ed 3 2005 EN 61000 6...

Страница 3: ...e operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At...

Страница 4: ... only at the sides of the display part not at the top nor bottom Display A large 60 x 60 mm display clearly shows actual room temperature and controller status with 7 segment digits and standard Day Night Off and Time scheduler symbols Active output is indicated by a heating symbol In the upper part there are week days used for time scheduler setup Other symbols are not used LCD symbol set ...

Страница 5: ... air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be considered together with design installation and operation of the entire control system which the device is part of ...

Страница 6: ...6 08 2018 Subject to technical changes domat UC905 Changes in versions 10 2017 The first datasheet version 08 2018 Minor changes ...

Отзывы: