domat UC095 

03/2017 Subject to technical changes. 

 

 

 

UC095 

Room  unit  for  VAV  controller 
FC015 

 

 

 

 

 

 

 

Summary 
 

The  UC095  room  unit  is  a  communicative  human-machine  interface  for  VAV  unit 
controller FC015. 

Application 
 

 

VAV systems 

 measurement and control of room temperature and CO

2

 

concentration 

Function 
 

The unit reads room temperature and CO

2

 concetration in the room air, temperature 

correction / setpoint by a knob, and required operation mode which is set by a short 
push or in the menu. Data is transmitted to the room controller. The main controller, 
FC015, may send to the unit other data (heating / cooling mode, fan stage, day / night 
/ standby mode etc.) which are displayed on the LCD display.  
 
Connect the room unit to FC015 over a 4 core cable, the most suitable types are JY(St)Y 
or LAM 2x2x0.8. Use the same type which powers the FC015 controller as if the room 
unit power is taken from the FC015 terminals, the cores in a terminal should be of the 
same cross-section. 
 

Technical data 
 

Power supply 

24 V st +/- 10% 

Consumption 

600 mVA 

Measuring range 

0 ÷ 50 °C

 

Protection 

IP20 

Sensor accuracy 

+/- 1,5 K (with software correction) 

Setpoint 

as configured, +/- 10 to +/- 1 K 

CO

2

 measuring range 

0 ... 2000 ppm 

CO

setpoint 

800 ppm by default 

CO

measuring method 

NDIR (Non-dispersive Infra Red) 

Содержание UC095

Страница 1: ...The main controller FC015 may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FC015 over a 4 core cable the most suitable types are JY St Y or LAM 2x2x0 8 Use the same type which powers the FC015 controller as if the room unit power is taken from the FC015 terminals the cores in a terminal should ...

Страница 2: ...RS485 Modbus RTU galvanically separated up to 3 kV Display LCD 60 x 60 mm Terminals screw terminals for wires 0 14 1 5 mm2 Cover ABS RAL9010 other colours Weight 0 13 kg Dimensions see below Terminals 1 2 3 4 5 6 7 1 K communication RS485 2 K communication RS485 3 NC not connected 4 NC not connected 5 GND technical earth TE 6 NC power common point 7 NC power Dimensions All dimensions in mm ...

Страница 3: ...d cabling connected first and the upper part inserted after the construction works have been finished to prevent damage to the unit Seal the conduits to avoid influencing the sensor by draught Use insulating pad when installing the sensor on cold walls Avoid sensor exposition to sunlight or other heat sources Opening the cover When removing the display part proceed as follows press gently the side...

Страница 4: ...4 03 2017 Subject to technical changes domat UC095 Changes in versions 08 2016 Changed format 03 2017 Added picture and description of the installation and link on the datasheet with other colours ...

Отзывы: