background image

 

08/2018 Subject to technical changes. 

domat UC010 

Temperature measuring range 

-

20 ÷ 70 °C

 

(accuracy ±1 ˚C) 

 

Humidity measuring range 

10 ÷ 90 rH (accuracy ±3 % rH) 

 

Setpoint  

as configured, +/- 10 to +/- 1 K 

Display 

LCD 60 x 60 mm 

Terminals 

screw terminals for wires 0,14 

 1,5 mm

2

 

Cover 

ABS, RAL9010, 

other colours

 

Protection 

IP20 

Weight 

0,13 kg 

Dimensions 

90x115x30 mm 

Ambient temperature 

External conditions: -5 

 45 

°C; 5 –

 95 % relative 

humidity;  non-condensing  gases  and  chemically 
non-aggressive  conditions  (according  to  EN 
60721-3-3 climatic class 3K5 

Storage:  -5 

  45 

°C;  5  –

  95 %  relative  humidity; 

non-condensing  gases  and  chemically  non-
aggressive conditions (according to EN 60721-3-1 
climatic class 1K3) 

Standards conformity 

EMC  EN  61000-6-2  ed.3:2005,  EN  61000-6-4 
ed.2:2006 + A1:2010 (industrial environment) 

Electrical safety EN 60950-1 ed.2:2006 + 
A11:2009 + A12:2011 + A1:2010 + A2:2014 + 
Opr.1:2012 + Z1:2016 

Hazardous substances reduction EN 50581:2012 

 
Version UC010DK without knob and display is available. 
Version with display and without knob is also available, need to be specified in order. 

Terminals 

1

2

3

4

5

6

7

 

 

1: NC   not connected 
2: NC   not connected 
3: K- 

 communication, RS485 

 

4: K+   communication, RS485 + 
5: GND   technical earth (TE) 
6: G0   power 

 common point 

7: G 

 power 

 

Содержание UC010

Страница 1: ...e menu Data is transmitted to the fancoil controller The fan coil controller may send to the unit other data heating cooling mode fan stage day night standby mode etc which are displayed on the LCD display Connect the room unit to FCR010 over a 4 core cable the most suitable types are JY St Y or LAM 2x2x0 8 Use the same type which powers the FCR010 controller as if the room unit power is taken fro...

Страница 2: ...ic class 3K5 Storage 5 45 C 5 95 relative humidity non condensing gases and chemically non aggressive conditions according to EN 60721 3 1 climatic class 1K3 Standards conformity EMC EN 61000 6 2 ed 3 2005 EN 61000 6 4 ed 2 2006 A1 2010 industrial environment Electrical safety EN 60950 1 ed 2 2006 A11 2009 A12 2011 A1 2010 A2 2014 Opr 1 2012 Z1 2016 Hazardous substances reduction EN 50581 2012 Ver...

Страница 3: ...e operated easily and measure correct values of temperature i e in the height of about 150 cm with no direct sunlight or other heat cool source AHU outlets refridgerator electrical appliances The device consists of two parts bottom with screw terminal block and cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm At...

Страница 4: ...en changing between the Comfort and Standby modes the controller falls back into automatic fancoil stage control according to the control deviation Operation mode change The operation mode in the Hotel mode used for fancoils in hotels and offices is changed over bus communication or by activating digital inputs The DI1 switches between the Comfort and Standby modes e g card reader while DI2 brings...

Страница 5: ...t temp Heating Night mode Temperature Heating Night are flashing Setpoint temp Heating Off mode Temperature Heating Empty house are flashing Setpoint temp Cooling Day mode Temperature Cooling Day are flashing Setpoint temp Cooling Night mode Temperature Cooling Night are flashing Setpoint temp Cooling Off mode Temperature Cooling Empty house are flashing Select the requested value by a short push ...

Страница 6: ... air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks related to device operation must be considered together with design installation and operation of the entire control system which the device is part of ...

Страница 7: ...hanged the format and reference to the configuration software 03 2017 Added picture and description of the installation and link on the datasheet with other colours 07 2017 Change of technical data standards and images BL version added 08 2017 Controller description change FC to FCR version 08 2018 Minor changes ...

Отзывы: