TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-37
Monday
, November 26, 2001 1:09 pm
Trip/Close Range
Selection
Currents
The following ranges are available:
• Trip Current Range: 0-2; 0-5; 0-20; 0-100 A
• Close Current Range: 0-0.2; 0-1; 0-5; 0-20 A
Trip Pulse
(Timing)
The trip pulse is adjustable in 1/10
ms increments. Select a pulse length
that is long enough to allow the
X
relay to drop out and de-energize the
coil.
The trip pulse is:
• 66.6 ms at 60 Hz
• 80 ms at 50 Hz
Select a trip pulse length that is long enough to allow the
A
switch to
de-energize the trip coil.
Close Pulse
(Timing)
The close pulse is adjustable in 1/10
ms increments. Select a close pulse
length that is long enough to allow the
X
relay to drop out and
de-energize the close coil.
Main Contact timing tabulation can be initiated from the following
timing event selections:
• Test Initiation (T0)
• Close Current
• Analog
• AUX Contact
N
OTE
Changing the Close Timing Event only affects the tabulated test results
for a Close test.
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...