Configuring Test Plans
There are two types of Test Plans:
• Library Test Plan
• Breaker Test Plan
A Library Test Plan contains the information required to run a general test
on a breaker type. This plan is flexible, in that none of the nameplate
information stored in this format is specific to a particular circuit breaker.
The Library Test Plan can be used repeatedly as a basis for configuring
multiple tests with the same basic test configuration, and on circuit
breakers of the same type.
A Breaker Test Plan is created when any circuit breaker-specific
information is entered in the nameplate on the
Test Plan
tab. Once such
information is entered, the title on top of the
Test
Plan
tab changes from
Library Test Plan
to
Breaker Test Plan
. This occurs by entering
information into
any
of the following fields:
• Manufacturer
• Serial Number
• Location
• Special ID
Both Test Plan types minimize the time required to configure tests as they
store common circuit breaker testing information and test parameters.
Items that can comprise a Test Plan include:
• Circuit breaker ID, such as type, serial number and manufacturer
• Range selection for Trip/Close currents
• Circuit breaker specifications and measurement zones, as
specified by the manufacturer
• Units of measurement (seconds or cycles, English or Metric)
• Transfer function for motion measurements
• Channel activation
• Performance specifications
N
OTE
The TDR9000 can be used in either the 50 or 60 Hz environment. This
selection is made using the TRX Options window accessed from the
TRXField View pulldown menu. For a complete description of this
window, refer to page A-31.
The TRXField software opens with the
TRXField for TR3000 and
TDR9000
dialog box open (Figure 4.15).
Содержание TDR9000
Страница 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Страница 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...