FX4C

FY4A

Installation Instructions

Direct Expansion Fan Coil Units

For Puron

r

Refrigerant

Sizes 018 To 060

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

HEATER PACKAGES

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Equipment

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Mount Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Ducts

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Connections

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Tubing Connection and Evacuation

10

. . . . . . . .

Refrigerant Flow--Control Device

10

. . . . . . . . . . . . . . . . . . .

Condensate Drains

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessories

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sequence of Operation

13

. . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP PROCEDURES

13

. . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

13

. . . . . . . . . . . . . . . . . . . . . .

PURON

R

(R--410A) QUICK REFERENCE GUIDE

14

. . . . .

SAFETY CONSIDERATIONS

Improper

installation,

adjustment,

alteration,

service,

maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause personal injury or property

damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories

when modifying this product. Refer to the individual instructions
packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for brazing operations. Have fire extinguisher

available. Read these instructions thoroughly and follow all

warnings or cautions attached to the unit. Consult local building
codes and National Electrical Code (NEC) for special

requirements.
Recognize safety information. This is the safety--alert symbol

. When you see this symbol on the unit and in instruction

manuals, be alert to the potential for personal injury.
Understand

the

signal

words

DANGER,

WARNING,

CAUTION, and NOTE. These words are used with the

safety--alert symbol. DANGER identifies the most serious
hazards which

will

result in severe personal injury or death.

WARNING signifies hazards which

could

result in personal

injury or death. CAUTION is used to identify unsafe practices

which

may

result in minor personal injury or product and

property damage. NOTE is used to highlight suggestions which

will result in enhanced installation, reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing unit, always turn off all power

to unit. There may be more than 1 disconnect switch. Turn

off accessory heater power, if applicable.

!

WARNING

INTRODUCTION

Models FX4C and FY4A are designed for flexibility and can be
used for upflow, horizontal, or downflow (kit required) and

manufactured and mobile home applications. These units are
designed to meet the low air leak requirements currently in effect.

Because of this, the units need special attention in the condensate

pan and drain connection area and when brazing tubing. These
units are designed specifically for Puron

r

refrigerant and must be

used only with Puron

r

refrigerant air conditioners and heat

pumps as shipped. These units are available for systems of

18,000 through 60,000 Btuh nominal cooling capacity.
Factory--authorized, field--installed electric heater packages are

available in sizes 5 through 30kW. See Product Data literature for

available accessory kits.

HEATER PACKAGES

This unit may or may not be equipped with an electric heater

package. For units not equipped with factory--installed heat, a
factory--approved, field--installed, UL listed heater package is

available from your equipment supplier. See unit rating plate for a
list of factory--approved heaters. Heaters that are not factory

approved could cause damage which would not be covered under

the equipment warranty. If fan coil contains a factory--installed
heater package, minimum circuit ampacity (MCA) and maximum

fuse/breaker may be different than units with a same size
field--installed accessory heater. The differences is not an error

and is due to calculation difference per UL guidelines.

INSTALLATION

Step 1—Check Equipment

Unpack unit and move to final location. Remove carton taking
care not to damage unit. Inspect equipment for damage prior to

installation. File claim with shipping company if shipment is
damaged or incomplete.
Locate unit rating plate which contains proper installation

information. Check rating plate to be sure unit matches job
specifications.

Содержание FX4C

Страница 1: ...hlight suggestions which will result in enhanced installation reliability or operation ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing unit always turn off all power to unit There may be more than 1 disconnect switch Turn off accessory heater power if applicable WARNING INTRODUCTION Models FX4C and FY4A are designed for...

Страница 2: ...k between duct unit and floor NOTE To convert units for downflow applications refer to Installation Instructions supplied with kit for proper installation For slope fan coils use kit Part No KFADC0201SLP For A coils use kit Part No KFADC0401ACL Use fireproof resilient gasket 1 8 to 1 4 in thick between duct unit and floor NOTE Gasket kit number KFAHD0101SLP is also required for all downflow applic...

Страница 3: ...RY DRAIN 1 3 4 IN FILTER ACCESS CLEARANCE A05173 Fig 2 Slope Coil Unit in Horizontal Left Application A B C FACTORY SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HORIZONTAL DRAIN PAN REFRIGERANT CONNECTIONS SECONDARY DRAIN HORIZONTAL LEFT PRIMARY DRAIN HORIZONTAL LEFT COIL SUPPORT RAIL COIL BRACKET DRAIN PAN SUPPORT BRACKET COIL BRACKET A00072 Fig 3 A Coil in Horizontal Left Application Fa...

Страница 4: ...ing 4 screws See Fig 6 b Remove air splitter B from coil seal assembly by removing 3 screws See Fig 6 factory shipped inset c Remove filter plate A and install air splitter B in place of filter plate d Install filter plate A as shown in horizontal right application e Remove condensate troughs C and install on opposite tube sheets f Install hose onto plastic spout 7 Install horizontal pan on right ...

Страница 5: ...al Right Applications Using a Slope Coil COIL SUPPORT RAIL COIL BRACKET DRAIN PAN SUPPORT BRACKET COIL SUPPORT RAIL COIL BRACKET HORIZONTAL DRAIN PAN PRIMARY DRAIN HORIZONTAL RIGHT SECONDARY DRAIN HORIZONTAL RIGHT REFRIGERANT CONNECTIONS AIR SEAL ASSEMBLY A B C HORIZONTAL RIGHT APPLICATION A00071 Fig 6 Conversion for Horizontal Right Applications Using A Coil FX4C FY4A ...

Страница 6: ...brous glass ducts Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts Step 4 Electrical Connections All products from the factory utilize a printed circuit board PCB which has a low voltage circuit protective fuse 5 amp fan motor speed tap selection terminal SPT and time delay relay TDR jumper To disa...

Страница 7: ...AOT0301FST for 2 outdoor thermostat systems CAUTION The controls are factory circuited for single stage operation For 2 stage operation use outdoor thermostat kit Part No KHAOT0301FST and for 3 stage use both kits Part No KHAOT0201SEC and KHAOT0301FST When 2 stages are desired cut W3 at the W2 wire nut strip and reconnect per the thermostat kit instruction See Fig 13 When 3 stages are desired cut ...

Страница 8: ...CONTROL RED GRY BRN WHT BLU VIO A94060 Fig 12 Wiring Layout Heat Pump Unit Cooling and 2 Stage Heat with No Outdoor Thermostat R G C E L O Y THERMOSTAT R R C O Y G C W2 W2 W2 W3 E ODTS FAN COIL CONTROL HEAT PUMP CONTROL RED GRY BRN WHT VIO BLU A94061 Fig 13 Wiring Layout Heat Pump Unit Cooling and 2 Stage Heat with 1 Outdoor Thermostat R G C L E O C 1 4 7 C 9 6 3 Y THERMOSTAT R R C O Y G C W2 W2 W...

Страница 9: ...L HEAT PUMP CONTROL G C W2 E L G C R O Y ODTS O Y W3 W2 A03088 Fig 15 Wiring Layout Heat Pump Unit Cooling and 2 Stage Heat for Manufactured Housing 230 C 208 BRN RED YEL BLK SECONDARY PRIMARY A01050 Fig 16 Transformer Connections FX4C FY4A ...

Страница 10: ... silver bearing or non silver bearing brazing materials Do not use solder materials which melt below 800_F Consult local code requirements 4 Evacuate coil and tubing system to 500 microns using deep vacuum method PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product or property damage Wrap a wet cloth around rear of fitting to prevent damage to TXV and factory made joints CAUT...

Страница 11: ...e Trap NOTE When connecting condensate drain lines avoid blocking filter access panel thus preventing filter removal After connection prime both primary and secondary condensate traps NOTE If unit is located in or above a living space where damage may result from condensate overflow a field supplied external condensate pan should be installed underneath the entire unit and a secondary condensate l...

Страница 12: ...t R FAN RELAY NO 230VAC COM NC NONC SPT WIRE NUT TO BLOWER MOTOR CONVERSION KIT TRANSFORMER FROM MOLEX PLUG AND TRANSFORMER IN UNIT TO EAC 208 230VAC COM 24VAC COM 208 230 COM CONTROL BOARD G T C C C A03011 Fig 21 Wiring Layout of Electronic Air Cleaner to Fan Coil for FY4A Models Only R G C E L O Y THERMOSTAT R R C O Y G C W2 W2 W2 W3 E FAN COIL CONTROL HEAT PUMP CONTROL RED GRY BRN WHT WHT BLU V...

Страница 13: ...stat closes R to W W energizes electric heat relay s which completes circuit to heater element s Blower motor is energized through normally closed contacts on fan relay When W is de energized electric heat relay s opens START UP PROCEDURES Refer to outdoor unit Installation Instructions for system start up instructions and refrigerant charging method details UNIT COMPONENT HAZARD Failure to follow...

Страница 14: ... hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth when brazing S A factory approved liquid line filter drier is required on every unit S Do NOT use an R 22 TXV S If indoor unit is equippe...

Отзывы: