XR20ATM  QUICK START GUIDE

1. System Components

Remove all items from the box. Depending on the Kit ordered, the box 

contains the following items:

KIT-ATM-D (Dial-Up)

•  One XR20ATM board in Enclosure with cover and mounting screws, 

36 inch battery wires, and resistor pack

•  One Model 321 40VA Plug-in Transformer

•  One Model 306 2-Wire Harness

•  Two Tamper Switches

KIT-ATM-N (Network with Dial-Up Backup)

•  All of the items in KIT-ATM-D

•  One  iCOM

SL 

Internet Alarm Router

•  One Model 330 4-Wire Harness

2. Reference Information

System Grounding

Connect a 14 AWG or larger wire from XR20ATM panel terminal 4 to a 

good Earth Ground.  DMP recommends a cold water pipe ground, building 

ground, or a ground rod.  

Do not

 connect to an electrical ground, conduit, 

sprinkler or gas pipes, or to a telephone company ground.

System Wiring

All wiring must be in accordance with NEC, ANSI, and NFPA 70.  Use non-

shielded 22 AWG wire up to 500 ft or non-shielded 18 AWG wire up to 1000 

ft from the panel.  Refer to the LX-Bus/Keypad Bus Wiring Note (LT-2031).

Reference Documents

As needed during installation, refer to the wiring diagram on the back, 

the XRSuper6, XR20, XR40 Installation Guide (LT-0624), XRSuper6/XR20/

XR40 Programming Guide (LT-0305), iCOM

SL

 Guide (LT-0631), and any 

documentation included with the system components.

Power Reference 

Remove all Power! 

Remove all AC and battery power from the panel 

before installing or connecting any modules, cards, or wires.

3. Remove the Enclosure Cover

Remove the enclosure cover and set aside.

4. Connect the Transformer

Connect the transformer wires through one of the enclosure knockouts to 

panel terminals 1 and 2. Use no more than 70 ft. of 16-gauge, or 40 ft. of 

18-gauge wire between the transformer and the panel.

5. Wire the Battery

Note: Observe polarity when connecting the battery.

Run the battery wires through one of the enclosure knockouts. Connect 

the black lead to terminal 4 (B-) on the XR20ATM. After wiring all devices, 

connect the red battery lead to terminal 3 (B+).

6. Specific ATM Software Features

The XR20ATM software does not require a panel reset to enter 

programming mode.  No opening or closing checks or scheduling 

options are available.  The Communication Network Trouble option 

is only available when using the KIT-ATM-N with an iCOM

SL

.  Set the 

Communication features as shown.

Programming

Enter 6653 (PROG) code to input initial data or make changes.

Communication

NET TRBL

NO 

 

 

YES

  Network Trouble 

Enables the network fail notification option.  

Set 

NET TRBL 

to 

YES

TEST FREQ

-

  Test Frequency

Allows you to set how often the panel sends a 

test report to the receiver.  Enter from 1 to 24 

hours.  

TEST FREQ

 default is 24 hours.  Enter 

zero to disable the test report.

Operation

Typically, wire Zone 1 to the lock to short out when the ATM is locked.  

Program Zone 1 as zone type AR and Style Maintain.  Assign this zone to 

Area 1.  Wire Zone 2 to the door contact and program as zone type NT.  

Assign this zone to Area 1.  When the ATM is unlocked, Zone 1 disarms 

the ATM.  When the ATM is locked, Zone 1 arms the ATM.  

Arm/Disarm 

When the ATM unit is accessed for programming or maintenance, 

the system disarms.  When the ATM unit is closed after completing 

programming or maintenance, the system arms.

Forced Arming

If the ATM is unlocked and disarmed for 30 minutes, the panel sends 

an S06 (Panel not Armed by Scheduled Time) message to the central 

station.  Then, after a ten minute window expires, if the system is not 

armed, the panel force arms the entire system. 

7. Program the XR20ATM Panel

Use a 4-wire keypad programming harness to connect an LCD Keypad to 

the XR20ATM.  Program the panel options.  Remove the programming 

harness and keypad.

8. Connect Model 306 2-Wire Harness

The 2-Wire Harness is used to supervise the RJ connectors and circuit to 

ensure ATM security.  Splice one 1K EOL resistor into one wire.  Connect 

that wire to any GND terminal.  Connect the remaining wire to any zone 

terminal.  Plug the other end of the 2-Wire Harness onto J7.

9. Connect and Mount Tamper Switches

The enclosure contains pre-drilled tamper switch mounting holes.  The 

back tamper switch installs with the button protruding out the pre-drilled 

hole in the enclosure back.  The front tamper switch installs with the 

button protruding past the enclosure edge.  Run one wire between the two 

tamper switches.  Splice one 1K EOL resistor into the second wire running 

from the front tamper switch.  Connect that wire to any GND terminal.  

Connect the second wire running from the back tamper switch to any zone 

terminal.

10. Connect the iCOM

SL

Connect the 4-wire harness to the J3 header on the iCOM

SL. 

 Connect 

the other end of the 4-wire harness to Programmer Header J8.  Be sure 

to connect the red wire where indicated at each end of the harness.  

Connect the Ethernet cable from your network to the Network Connector 

(J4) on the iCOM

SL. 

11. Program the iCOM

SL

Use a 4-wire keypad programming harness to connect an LCD Keypad to 

the iCOM

SL

.  Remove the programming harness and keypad.

���
������
����

����������

�������
�����������

���������������
�������������

�����

������������

���������

���������

�������

�����

�������������

���������������
�����������������
�����������
��������������
�����������������

���

��������������������������������������
������������������������������������������

���

��

��

��

���

����

��

������

���

������������

���




�������

���������������������������������

�������������������������

���������������
����������������
���������������

��

��

��

��

��

��

��

��

��

��

��

��

��

��

���� ���

���

��� ��� ��� ���

��

��

��

��

��

��

��

���

���

���

���

��

��

��

��

��

��

��

��

��

���� ����

������
�������

12. Wiring Zones

Wire zones as desired. 

Note:

 Use one 1K EOL resistor on each zone 1-9.  Use 

one 3.3K EOL resistor on Zone 10.  

13. Mount the iCOM

SL

Mount the iCOM

SL

 unit on the top edge of the enclosure. 

Begin with the iCOM

SL 

connector end.  Slide the edge 

of the casing onto the enclosure top edge. Firmly press 

the iCOM

SL 

casing until the entire side overlaps the 

top edge of the enclosure.  Slide the iCOM

SL

 unit away 

from the heat sink to allow adequate air flow inside the 

enclosure.