Connect Popex and Octopopit Modules
Connect the Radionics POPEX™ and OctoPOPIT ™ modules to the Zone Expander
terminals on 736P. The maximum wire distance between the 736P and any Radionics
POPEX and OctoPOPIT is 10 feet. For more information about wiring specifications,
refer to Additional Information. Refer to Figure 4 when connecting POPEX and
OctoPOPIT modules to the 736P.
1.
Connect wires from the 736P Zone Expander to the POPEX or OctoPOPIT
module as follows:
a. COM Terminal to COM Terminal
b. DOUT Terminal to IN Terminal
c. ZX Terminal to OUT Terminal
d. +AUX Terminal to AUX Terminal
2. Select the type of Radionics ZONEX™ Bus that connects to the 736P module.
To select a 63‑point (horizontal or vertical) bus, place a jumper across the
top two 63/119 pins. To select the expanded, 119‑point bus, place the jumper
across the bottom two 63/119 pins.
Because the Radionics D8125 Zone Expander is rated to operate over a voltage range
of 10.2 VDC to 14 VDC, a power supply must be listed for fire protective signaling
systems, power limited, and provide a voltage range within 10.2 VDC to 14.0 VDC.
Refer to Figure 5.