Wire the Zone Terminals
Terminals 5 through 9 connect grounded zones 1 through 3. These zones have a
grounded side and cannot be used for fire‑initiating devices. Zones 2 and 3 can
also be used for access control with Zone 2 providing a bypass option and Zone 3
providing Request to Exit functionality. Zone 4 terminals provide a non‑powered
Class B, Style A zone.
Use the supplied DMP Model 311 1k Ohm End‑of‑Line resistors on each zone. Refer to
the panel programming guide for programming instructions. See Figure 9 for more
information on wiring the zone terminals.
Auxiliary Outputs 1 & 2
The module controls Auxiliary Outputs 1 and 2 when the Activate Zone 2 Bypass
programming option is enabled and the Zone 2 Bypass Time is set. When the door
contact (zone 2) is opened while the door strike is activated, the Zone 2 Bypass
Time starts. If the door has not closed at the end of the timer, Aux Output 1 is turned
on and the timer starts again. If the door is still open at the end of the second timer,
Aux Output 2 is turned on. Aux Outputs 1 and 2 turn off when the door contact is
closed. Use the Model 431 Relay Harness for connection of Output 1 and Output 2.