No Communication with Panel
Define the relay action when communication with the panel
has not occurred for 5 seconds:
OFF
,
SITE
,
ANY
,
ON
, or
LAST
. Default is
OFF
. Press any select key or area to change
the default relay action:
Press the first select key or area to choose
OFF
(Relay
Always Off). The relay does not turn on when any Wiegand
string is received.
OFF
does not affect any REX operation. If
communication is lost during a door strike, the relay remains
on for the door strike duration but turns off at the end of the
door strike timer.
Press the second select key or area to choose
SITE
(Accept
Site Code). Door access is granted when the Wiegand site
code string received matches any site code programmed at
Site Code. Refer to “Require Site Code” for more information.
Press the third select key or area to choose
ANY
(Any
Wiegand Read). Access is granted when any Wiegand string
is received.
Press the fourth select key or area to choose
ON
(Relay
Always On). The relay is always on.
Press
CMD
to display additional actions. Press the first
select key or area to choose
LAST
(Keep Last State). The
relay remains in the same state and does not change when
communication is lost.
NO COMM WITH PNL
OFF
OFF
SITE ANY ON
OFF
SITE
ANY ON
OFF SITE
ANY
ON
OFF SITE ANY
ON
LAST