Set the 734INT Address
To set the 734INT address, move the DIP switches on the PCB to the appropriate
positions. See the following sections, Figure 10, and Table 2 to determine how to set
Keypad Bus or AX‑Bus addresses.
7
Keypad Bus Addresses Explained
Each Keypad Bus address can accommodate one door output and four expansion
zones. A 734INT with an address of 2 on the Keypad Bus would represent
door 2 and zones 21‑24. A 734INT with a keypad address of 14 would represent
door 14 and zones 141‑144.
AX‑Bus Addresses Explained
XR550INT panels are capable of access control expansion using any of the five
AX/LX‑Bus headers (AX/LX500, 600, 700, 800, and 900). An AX‑Bus address
can accommodate one door output and one expansion zone. Because the 734INT
has a built‑in four‑zone expander, three extra zones will be mapped to the 734INT
automatically.
A 734INT with an address of 1 on AX500 would represent door 501 and
zones 501‑504. A 734INT with an address of 2 on AX500 would represent
door 505 and zones 505‑508. A 734INT with an address of 1 on AX700 would
represent door 701 and zones 701‑704.
Note:
Hardwired zone expanders and modules do not communicate on an
AX‑Bus. Doors connected to the AX‑Bus do not have programmable device or
communication types and do not have assignable display areas.