711S ZONE EXPANSION MODULE

Installation Guide

DESCRIPTION

Figure 1: 711S Zone Expansion Module

The 711S is a flying lead style, 

single-zone, addressable expansion 

module that allows you to increase 

the number of reporting zones 

available on DMP panels. Refer to 

the panel installation guide for more 

information about zone expansion 

modules and the maximum number 

allowed per panel. The modules 

connect to the panel 4-wire Keypad 

Bus or LX-Bus™ and are set to 

an address that determines the 

reporting zone number. The 711S 

provides one Type A Class B zone.

Compatibility

All XT30/XT50 and XR150/XR550 

Series Panels.

What is Included?

• 

711S Expansion Module

• 

1k Ohm Resistor

1

ADDRESSING THE 711S MODULE

The 711S addressable zone expansion module is for use in smaller 

applications, such as installing in a pull station back-box or even in a 

recessed contact hole behind the contact.

LX-Bus Zone Numbers

Refer to Table 2 for a partial list of XR550 Series panel LX-Bus zone 

numbers. XR150 Series panels only use LX500. For LX-Bus addresses set 

the switches to match the last two digits of the address.

Setting Address Switches

The 711S Zone Expander uses two rotary switches identified as TENS and 

ONES to set the module address. Use a small 

screwdriver to set the address accordingly for 

Keypad Bus (See Table 1) or LX-bus (See Table 2). 

For example, for address 

502

 on an XR550 Series 

panel set the 

TENS 

switch to zero and the 

ONES 

switch to two as shown in Figure 2. 

LX-Bus 

Address

LX-Bus 

Number

Switches 

   Tens 

Ones

Zone 

Number

501

1(LX500)

0

1

501

506

1(LX500)

0

6

506

623

2(LX600)

2

3

623

654

2(LX600)

5

4

654

742

3(LX700)

4

2

742

768

3(LX700)

6

8

768

833

4(LX800)

3

3

833

877

4(LX800)

7

7

877

919

5(LX900)

1

9

919

994

5(LX900)

9

4

994

Table 2: Example LX-Bus Zone Numbers

Keypad Bus Zone 

Numbers

The 711S module uses the first 

zone number only. The last three 

zone numbers cannot be used 

for other devices. For example, 

turn the 711S switches to address 

02 (

TENS 

= 0, 

ONES 

= 2) to set 

the module zone number to zone 

21. Zones 22, 23, and 24 cannot 

be used.
Refer to Table 1 for Keypad Bus 

zone numbers and the panels 

where they operate.

Keypad 

Address

Switches 

Tens  Ones

Zone Number

XT30/50 XR150

XR550

1

0

1

11

11

11

2

0

2

21

21

21

3

0

3

31

31

31

4

0

4

41

41

41

5

0

5

51

51

51

6

0

6

61

61

61

7

0

7

71

71

71

8

0

8

81

81

81

9

0

9

N/A

N/A

91

10

1

0

N/A

N/A

101

11

1

1

N/A

N/A

111

12

1

2

N/A

N/A

121

13

1

3

N/A

N/A

131

14

1

4

N/A

N/A

141

15

1

5

N/A

N/A

151

16

1

6

N/A

N/A

161

Table 1: Keypad Bus Zone Numbers

INSTALLING THE 711S MODULE

Wiring the 711S Module

Connect the 

Red

Yellow, Green

, and 

Black

 wires from the panel Keypad 

Bus or LX-Bus™ to the matching wires on the zone expander.

Caution: Do not use looped wire under terminals if wiring directly 

to the Keypad bus. Break wire run to provide supervision of 

connections.

2

0

1

2 3 4

5

6

7

8

9

0

1

2 3 4

5

6

7

8

9

    

TENS          ONES