background image

521LX/521LXT Installation Sheet 

Digital Monitoring Products

3

Sensitivity Level Test Mode

Each smoke detector also includes a special sensitivity level test mode 

activated by holding a magnet near the integral reed switch for more than 

one second. See Figure 6. Once the routine starts, the alarm LED flashes 

one to nine times, indicating actual sensitivity and whether or not service is 

required. See the 

521 Sensitivity Table

.

After the sequence of blinks, if the sensitivity is found to be within limits and 

if all other tests pass, the detector goes into alarm until reset by the panel.
If the sensitivity is not within limits, or an unser viceable hardware fault is 

detected, the alarm LED con tinues to flash once per second until the detector 

is reset by the panel. If the sensitivity test is not within guidelines, take 

action as recommended in the 

521 Sensitivity Table

.

Approximate 

Obscuration (% ft.)

Blinks

Indication

Action

Photo

1

Reset unit and re-run sensitivity test, if 

indication remains the same, replace unit.

4.35

2

Detector is not sensitive enough.

Clean per instructions. Reset unit and re-run 

sensitivity test, if indication remains the same, 

replace unit.

3.85

3

3.60

4

Detector is within sensitivity 

limits.

None

3.10

5

2.60

6

2.10

7

1.85

8

Detector is too sensitive.

Check to be sure optical block cover is snapped 

down completely. Clean per instructions.

1.35

9

Table 1: 521 Sensitivity Table

Smoke Detector Dip Switches

If there are dip switches to the left of the screw terminals, they are factory preset and must not be changed.

Maintenance, Cleaning, and Sensitivity

The smoke detectors are designed for easy field service and maintenance. If a smoke detector drifts beyond its 

approved sensitivity range for more than 24 hours or fails internal diagnostic tests during power-up, the unit 

automatically indicates trouble by flashing its LED every second. Under normal conditions the LED flashes every nine 

seconds. Therefore, a simple visual check of the LED status meets NFPA 72 field sensitivity testing requirements 

without the need for external meters or ladders. In accordance with NFPA 72-7-3.2.1, smoke detector sensitivity 

should be checked within one year after installation and every alternate year thereafter, in commercial installations, 

or every three years in residential sites.
The photoelectric detector sensing chamber un snaps for easy field cleaning and service. Whenever the status LED 

indicates cleaning is necessary, remove the photoelectric detector cap, snap off and throw away the optical block. 

Then blow or brush off the optical block base and snap a new optical block chamber back in place (see Figure 5), 

replace the cap and verify sensitivity with the Sensitivity Level Test.

Figure 6: Sensitivity 

Testing the 521LX/521LXT

Reed 

Switch

Magnet

Отзывы: