InstallatIon sheet
464-263H HSPA+ Cellular Communicator
Description
The 464-263H HSPA+ Cellular Communicator provides a fully supervised alarm communication path over the HSPA+
network for XR100/XR500 Series panels. The 464-263H is installed in the panel enclosure and powered by the panel, so no
additional enclosure, power supply or battery back-up is needed.
What is Included
The 464-263H includes the following:
• One Model 464-263H Cellular Communicator
• One Model 381-2, 18-inch Coax cable with SMA connector
• One 4-Wire LX-Bus harness
• One SIM Card
• One Model 383 Rubber Duck Antenna
• One PCB standoff
Compatibility
The 464-263H is compatible with XR100 and XR500 Series control panels when
using version 212 or higher.
Installation Safety
Ground Yourself Before Handling the Panel!
To discharge
static, touch any grounded metal, such as the enclosure,
before touching the panel.
Remove All Power From the Panel!
Remove all AC
and Battery power from the panel before installing or
connecting any modules, cards, or wires to the panel.
Installing the 464-263H
Align the 464-263H card 50 pin connector with the J6 connector and
press the card onto the connector while applying even pressure to
both sides of the board. See Figure 2.
Installing the SIM Card
Insert the SIM
card into the 263H as pictured in Figure 1.
Connecting the Antenna
1. Position one of the supplied washers onto the 381-2 SMA
connector and push the threaded end through an enclosure
knockout.
2. Position the second washer onto the threaded end extending
through the knockout and secure the nut.
3. Attach the included 383C Antenna to the SMA connector.
See Figure 2.
4. Attach the opposite end of the 381-2 Coax to the SMA connector
on the
464-263H. See Figure 2.
Note:
As an alternative, the antenna coax can be connected directly to the
464-263H SMA connector when the coax enters the enclosure via conduit.
LX-Bus™ Expansion Capability
The 464-263H card also provides a 4-wire LX-Bus™ for the addition of
any combination of 100 protection zones and 100 relay outputs. Insert
the harness connector into the 4-pin LX-Bus header on the bottom of
the 464-263H Interface Card.
Note:
Do not use shielded wire when using the LX-Bus. Do not connect
the wires from the 464-263H to panel terminals or the panel J22
header. All devices installed on the 464 LX-Bus must be included in the
panel standby battery calculations.
Programming/Activation
Cellular Service is required before using the 464-263H for signal
transmission. In Remote Link panel communication programming,
select Cellular as one of the Communication types. The module comes
with a SIM card ready for activation with SecureCom Wireless, LLC.
More information is available at www.securecomwireless.com or refer
to the Remote Link Users Guide (LT-0565). Or, use a SIM card provided by
the carrier of your choice. If you are activating the unit with an
alternate carrier, program the APN provided by your carrier during panel programming.
65555
SIM
CARD
Bottom View
Figure 1: 263H SIM Card Installation
Model 381-2
Coax Cable
from 263H
Nut
Washers
SMA
Connector
SMA
Connector
Antenna
Connector
J6 Interface Card
Connector
18
19
20
21
22
23
24
25
26
27
28
Z5
Z6
Z7
Z8 Z9+ Z9- Z10+ Z10-
GND
GND
Red—Auxiliary Power
Yellow—Data In
Green—Data Out
Zone Expansion
Harness Connector
To LX-Bus
Modules
XR100/XR500
Panel
Black—Ground
263H
Cell Module
464-263H
263H
SIM
Card
Figure 2: 464-263H HSPA+ Wiring
Figure 3: Remote Link Activation
Figure 4: Remote Link Activation