background image

Dixell

 

Instruction Manual

 

cod. 1592005010 

 

Error! Unknown switch argument.

 

XV110K - XV150K

Error! Unknown switch argument.

/

Error! Unknown switch argument.

 

XV110K - XV150K 

 

FAN SPEED CONTROLLERS 

 
 

CONTENTS 

GENERAL WARNING __________________________ 1 

GENERAL DESCRIPTION  ______________________ 1 

OPERATING _________________________________ 1 

COMMANDS _________________________________ 1 

DIRECT and INVERSE CONTROL ________________ 1 

CONTROLS __________________________________ 2 

ANTI CONDENSING KIT (optional) _______________ 2 

INSTALLING AND MOUNTING  __________________ 2 

ELECTRICAL WIRING  _________________________ 2 

10 

OUTPUT STATUS FOR FAULTY PROBE __________ 2 

11 

TECHNICAL DATA ____________________________ 2 

12 

CONNECTIONS _______________________________ 2 

13 

DEFAULT VALUES ____________________________ 2 

 

GENERAL WARNING 

1.1  Please read before using this manual 

 

This manual is part of the product and should be kept near the instrument 
for easy and quick reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those 
described hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2 

 Safety Precautions 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the 
operating  limits  avoiding  sudden  temperature  changes  with  high 
atmospheric humidity to prevent  formation of condensation 

 

Warning:  disconnect  all  electrical  connections  before  any  kind  of 
maintenance. 

 

The instrument must not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the 
distributor or to “Dixell s.r.l.” (see address) with a detailed description of 
the fault. 

 

Consider the maximum power of the load (see Technical Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are 
separated  and  far  enough  from  each  other,  without  crossing  or 
intertwining. 

 

Fit  the  instrument  away  from  heater  sources  and  be  sure  to  have  
sufficient air flow to allow a good thermal exchange.  

GENERAL DESCRIPTION 

The  models 

XV110K

  (1000Watt)  and

  XV150K

  (5000Watt)  are  speed 

controllers suitable for industrial and refrigeration applications in particular to 
control the air flow in condensing and evaporating and condensing processes. 
The regulation is made through 4 trimmers placed on the board while the load 
control is executed by a TRIAC with phase cut. 
The controllers are configurable to start the fans at the maximum speed for 10 
seconds. The input signal can be ordered choosing among temperature probe 
NTC, 4/20mA or 0/1Vdc and 0/10Vdc signals. 

OPERATING 

Example of functioning with a condensing unit (direct): the probe must be fit 
where the sensor detects the most critic place of the condenser. Calibrate the 
Set  trimmer  to  the  temperature  (or  pressure)  at  which  the  fan  runs  at  the 
maximum  speed.  Then  calibrate  the  Diff  trimmer  to  set  the  temperature  (or 

pressure) differential at which the fan is stopped. E.g. if the Set is 40°C 
and the Diff is 10°C, when the temperature is above 40° the fan runs at 
maximum  speed,  if  the  temperature  is  between  30°  and  40°  the  fan 
speed is proportionally controlled. Below 30°C the fan is stopped. 

COMMANDS 

Trimmer SET

: by turning clockwise this trimmer, the set is changed from 

the minimum to the maximum value (see table of the default 
values). 

Trimmer differential:

 by turning clockwise this trimmer, the differential is 

changed from the minimum to the maximum value (see table of 
the default values). 

Trimmer  V  min:

  by  turning  clockwise  this  trimmer,  the  minimum  fan 

speed can be changed from 0 to 50% of the maximum voltage 
output. 

Trimmer Cut Off:

 by turning clockwise this trimmer, the fan cut-off can be 

changed from 10 to 30% of the maximum voltage output. 

Green led: 

this led

 

signals when the load is being controlled. 

DIRECT AND INVERSE CONTROL 

Direct  action

:  if  the  input  signal  increases,  the  voltage  output 

proportionally increases (condensing or cooling applications). 
 

 

 
 
If the input signal is higher than the Set, the output signal is 230 Volt (fans 
are  running  at  the  maximum  speed).  When  the  signal  decreases  and 
enters the range between the Set and Set-Diff the output signal follows 
the  temperature  variation. Below the Set-diff  value the output signal is 
always 0V (if no Vmin has been set). 

 
Inverse  action

:  if  the  input  signal  increases,  the  voltage  output 

proportionally decreases (evaporating or heating applications). 
 

 

 

 
If the input signal is lower than the Set, the output signal is 230 Volt (fans 
are  running  at  the  maximum  speed).  When  the  signal  increases  and 
enters the range between the Set and Set+Diff the output signal follows 
the temperature variation. Above the Set+diff  value the output signal is 
always 0 Volt (if no Vmin has been set). 