MT-KOS206TC_EN_20181217

 

KOS

206TC USER GUIDE 

SMART HEAD MOUNT THERMOCOUPLE TRANSMITTER 

TWO WIRE (4 to 20) mA OUTPUT 

Important - Please read this document before installing. 

Every effort has been taken to ensure the accuracy of this document, however we do 

not accept responsibility for damage, injury, loss or expense resulting from errors and 

omissions, and we reserve the right of amendment without notice. 

IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be mounted inside a suitable enclosure providing environmental 

protection to IP65 or greater. 

To maintain CE EMC requirements, input wires must be less than 3 metres. 

The product contains no serviceable parts, or internal adjustments. No attempt must 

be made to repair this product. Faulty units must be returned to supplier for repair. 

This product must be installed by a qualified person. All electrical wiring must be 

carried out in accordance with the appropriate regulations for the place of installation. 

Before attempting any electrical connection work, please ensure all supplies are 

switched off. 

ABSOLUTE MAXIMUM CONDITIONS (To exceed may cause damage to the unit). 
Supply Voltage 

± 30 V dc (Protected for over-voltage and reverse connection) 

Current with over-voltage 

± 100 mA 

Input Voltage 

± 3 V between any terminals 

Ambient 

Temperature (-40 to 85) °C, Humidity (10 to 95) % RH (Non-
condensing) 

-----------------------------------------------------------------------------------
-- 

1~DESCRIPTION.

The device is a “smart” in-head transmitter that accepts thermocouple temperature  

sensors and converts sensor output over a configured range to a standard industrial 

(4 to 20) mA transmission signal.  

PC configuration allows the user to select thermocouple type, range, units and 

burnout direction, without requiring calibration equipment. Configuration is performed 

quickly using our USB port-driven configurator. 

Calibration setup may be saved as a file on the PC for later use. If required the 

desired range can be specified at the time of order, removing the need for user 

configuration. 

2~RECEIVING AND UNPACKING

Please inspect the packaging and instrument thoroughly for any signs of transit 

damage. If the instrument has been damaged, please notify your supplier 

immediately. 

3~SPECIFICATION.

 

Refer to data sheet for full specification. 

Configuration 

Factory default 

Type K, (0 to 1000) °C, upscale burnout, 0.0°C offset 

4~INSTALLATION AND WIRING. 

 

Ø43.0 mm 

21.0 mm

 

33.0 mm

 

Centres 

Mounting holes: two holes 5.5 mm diameter, 33 mm centres.        

Centre hole sensor wire entry 4 mm. 

4.1~MECHANICAL. 

The unit is mounted using two 5.5 mm holes, on standard 33 mm fixing centres and will 

fit a DIN standard termination head. The unit must be installed with adequate protection 

from moisture and corrosive atmospheres.  

Care must be taken to ensure the unit is located so the ambient temperature does not 

exceed the specified operating temperature. 

4.2~ELECTRICAL. 

Electrical connections to the transmitter are made to the screw terminal provided on the 

top face. The transmitter is protected against reverse connection and over-voltage. If 

no sensor (input) connection is made, the transmitter will go into either up or down 

scale output current, depending on configuration setting. 

TURN OFF SUPPLY BEFORE WORKING ON ANY ELECTRICAL CONNECTION 

Input sensor connections. 

Thermocouple inputs must use correct compensation cable. 

Sensor connections are as follows: to maintain BS EN61326 compliance, sensor wires 

must be less than 3 metres. All sensor connections must be isolated from ground. 

U

-

+

-

+

R

M

T/C

LOAD

(4 to 20) mA Loop connections. 

Ensure all other aspects of the installation comply with the requirements of this 

document. To maintain CE compliance, the (4 to 20) mA current loop must be tied to a 

local earth at one point; this is normally at the power supply.  

Use twisted pair or screened cables for cable lengths greater than 30 metres. Maximum 

cable length 1000 metres.  

5~USER CONFIGURATION. 

 IMPORTANT 

READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION.  

IMPORTANT 

Do not attempt to configure the unit when connected to a loop supply. 

A USB configuration module is required for connecting the unit to the PC. Refer to your 

supplier for details. 

CONFIGURATOR

Download @ 

www.status.co.uk

USB SPEEDLINK

COMPUTER

Red +

Black -

Install the software and connect the USB configuration module 

Configuration steps 

Install the software and connect the USB configuration module to the PC. 

Connect the configuration module to the device (removed from any loop supply). 

Select the correct programming page in the software. 

Read the unit configuration into the software. 

Re-configure or adjust configuration options as required. 

Send the new configuration to the unit. 

Configuration options in software 

Thermocouple type 

From list 

Temperature units 

°C or °F 

Low range 4 mA 

Any °C/°F point within range 

High range 20 mA  

Any °C/°F point within range 

Sensor fail 

Burnout high or low 