KOS
206TC USER GUIDE
SMART HEAD MOUNT THERMOCOUPLE TRANSMITTER
TWO WIRE (4 to 20) mA OUTPUT
Important - Please read this document before installing.
Every effort has been taken to ensure the accuracy of this document, however we do
not accept responsibility for damage, injury, loss or expense resulting from errors and
omissions, and we reserve the right of amendment without notice.
IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be mounted inside a suitable enclosure providing environmental
protection to IP65 or greater.
To maintain CE EMC requirements, input wires must be less than 3 metres.
The product contains no serviceable parts, or internal adjustments. No attempt must
be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be
carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are
switched off.
ABSOLUTE MAXIMUM CONDITIONS (To exceed may cause damage to the unit).
Supply Voltage
± 30 V dc (Protected for over-voltage and reverse connection)
Current with over-voltage
± 100 mA
Input Voltage
± 3 V between any terminals
Ambient
Temperature (-40 to 85) °C, Humidity (10 to 95) % RH (Non-
condensing)
-----------------------------------------------------------------------------------
--
1~DESCRIPTION.
The device is a “smart” in-head transmitter that accepts thermocouple temperature
sensors and converts sensor output over a configured range to a standard industrial
(4 to 20) mA transmission signal.
PC configuration allows the user to select thermocouple type, range, units and
burnout direction, without requiring calibration equipment. Configuration is performed
quickly using our USB port-driven configurator.
Calibration setup may be saved as a file on the PC for later use. If required the
desired range can be specified at the time of order, removing the need for user
configuration.
2~RECEIVING AND UNPACKING.
Please inspect the packaging and instrument thoroughly for any signs of transit
damage. If the instrument has been damaged, please notify your supplier
immediately.
3~SPECIFICATION.
Refer to data sheet for full specification.
Configuration
Factory default
Type K, (0 to 1000) °C, upscale burnout, 0.0°C offset
4~INSTALLATION AND WIRING.
Ø43.0 mm
21.0 mm
33.0 mm
Centres
Mounting holes: two holes 5.5 mm diameter, 33 mm centres.
Centre hole sensor wire entry 4 mm.
4.1~MECHANICAL.
The unit is mounted using two 5.5 mm holes, on standard 33 mm fixing centres and will
fit a DIN standard termination head. The unit must be installed with adequate protection
from moisture and corrosive atmospheres.
Care must be taken to ensure the unit is located so the ambient temperature does not
exceed the specified operating temperature.
4.2~ELECTRICAL.
Electrical connections to the transmitter are made to the screw terminal provided on the
top face. The transmitter is protected against reverse connection and over-voltage. If
no sensor (input) connection is made, the transmitter will go into either up or down
scale output current, depending on configuration setting.
TURN OFF SUPPLY BEFORE WORKING ON ANY ELECTRICAL CONNECTION
Input sensor connections.
Thermocouple inputs must use correct compensation cable.
Sensor connections are as follows: to maintain BS EN61326 compliance, sensor wires
must be less than 3 metres. All sensor connections must be isolated from ground.
U
-
+
-
+
R
M
T/C
LOAD
(4 to 20) mA Loop connections.
Ensure all other aspects of the installation comply with the requirements of this
document. To maintain CE compliance, the (4 to 20) mA current loop must be tied to a
local earth at one point; this is normally at the power supply.
Use twisted pair or screened cables for cable lengths greater than 30 metres. Maximum
cable length 1000 metres.
5~USER CONFIGURATION.
IMPORTANT
READ COMPLETE SECTION BEFORE ATTEMPTING CONFIGURATION.
IMPORTANT
Do not attempt to configure the unit when connected to a loop supply.
A USB configuration module is required for connecting the unit to the PC. Refer to your
supplier for details.
CONFIGURATOR
Download @
www.status.co.uk
USB SPEEDLINK
COMPUTER
Red +
Black -
Install the software and connect the USB configuration module
Configuration steps
Install the software and connect the USB configuration module to the PC.
Connect the configuration module to the device (removed from any loop supply).
Select the correct programming page in the software.
Read the unit configuration into the software.
Re-configure or adjust configuration options as required.
Send the new configuration to the unit.
Configuration options in software
Thermocouple type
From list
Temperature units
°C or °F
Low range 4 mA
Any °C/°F point within range
High range 20 mA
Any °C/°F point within range
Sensor fail
Burnout high or low