MT-KOS1720_EN_20181217     User instruction guide

 

KOS

1720 

USER GUIDE

 

 

To avoid the risk of electric shock and fire, read this instruction document completely before using it.

.

 

Dual channel signal conditioner designed to accept RTD, Thermocouple or Potentiometer sensors and provide isolated, industrial process output signals in mA or 

Volts. Each output channel may be linked to either input sensor or to a maths function of both sensor signals. This powerful feature allows the device to operate in a 

number of different modes

.

DISEÑOS Y TECNOLOGÍA S.A., Xarol, 6B, P.I. Les Guixeres, 08915 Badalona, ESPAÑA

.

 www.dite

l.es

+34 933 394 758.

IMPORTANT SAFETY REQUIREMENTS.  

Max working voltage Terminals (101 to 104) and (201 to 204)  Inputs 

 ±24 Vdc @ 10 mA 

Max working voltage Terminals (105 to 108) and (205 to 208)  Outputs 

 ±30 Vdc @ 50 mA 

Max working voltage Terminals (S1 to S2) supply   

  240 Vac, ± 240 Vdc 

Isolation supply to Input/output 

  4200 V  

Any input to any Output 

  3750 V  

Output to Output, Input to Input  

3750 V 

This  equipment  is  suitable  for  environment  Installation  category  II  pollution  degree  1  and  is  classed  as  "PERMANENTLY  CONNECTED
EQUIPMENT". The equipment is intended for industrial and commercial application only and not suitable for domestic or medical use.

The equipment must be mounted inside an enclosure that provides protection >= IP65. In NORMAL USE, the equipment will only be accessed 
for maintenance by qualified personnel. Please ensure the equipment is mounted vertically with terminals (101 to 204) at the bottom. This
will provide maximum ventilation and correct cold junction compensation. This equipment may generate heat, ensure the enclosure size is
adequate to dissipate heat. Be sure to consider any other equipment inside the enclosure.

The equipment surfaces may be cleaned with a damp cloth. Use a mild detergent/water on a damp cloth. Ensure the supply is off before
cleaning and on completion of cleaning the equipment is completely dry before the supply is turned back ON.

The equipment contains no serviceable parts, or internal adjustments. No attempt must be made to repair the product. Faulty equipment 
must be returned to the supplier for repair.

This equipment must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate
regulations for the place of installation.

DC supply must be derived from a local supply and not a distribution system.

To maintain CE EMC requirements, voltage input, DC supply and voltage output wires must be less than 30 metres.

Supply (20 to 240) Vac 50/60 Hz (20 to 240) Vdc. If supply is a HAZARDOUS VOLTAGE a supply isolation switch must be installed close to
the equipment with the “OFF” position clearly marked. Also, the supply must be fused with a suitable 1 A (T) fuse (circuit breaker) installed 
close the equipment.

Receipt and unpacking. Please inspect packaging and instrument thoroughly for any signs of transit damage. If damage is present, do not 
use the equipment as safety protection may be affected. Please return damaged equipment to supplier. 

USB configuration can be performed without the supply being connected. For safety reasons, use 24 Vdc for functional test of unit prior to
fixed installation. The following operations should only be carried out on a disconnected device and under ESD safe conditions: General
mounting, connection and disconnection of wires.

Specification, please refer to supplier’s web site latest product data sheet for full specification. 
Basic specification 

Supply 

(20 to 240) Vac 50/60 Hz or (20 to 240) Vdc, 3 W, max isolation 4.2 KV supply to input output 
3.75 KV to all other ports 

Input (SELV) 

RTD, Thermocouple, Potentiometer. 

Output (SELV) 

Current (0 to 20) mA, Voltage (0 to 10) V 

Ambient 

(-20 to 70) °C Approvals EN61010_1, EN61326 

   

Configuration (Read the IMPORTANT SAFETY REQUIREMENTS)

 During configuration the equipment takes its power from the USB port, therefore 

no power supply connection is required. The equipment can be configured whilst powered but the computer used must be isolated from the supply earth to 
avoid grounded earth loop effects. To avoid electric shock only use a 24 Vdc supply during bench configuration.  

Device

USBSpeedLink software

www.status.co.uk

USB CABLE

COMPUTER

Default settings inputs PT100, outputs (4 to 20) mA, process ranges (0 to 100) °C, fail high, Tag Channel 1 Channel 2. 