Network Guide
Setting the Allure EC-Smart-Air and EC-Smart-Com-
fort Communicating Sensor Series' Subnet ID
Address
Each Allure EC-Smart-Air or EC-Smart-Comfort communicating sensor connected to a con-
troller's Subnet Port must be set to a unique subnet ID address. This address should corre-
spond to the block number of the associated Subnet Extension block in EC-
gfx
Program. The
address is set through a DIP switch located inside the sensor near the RJ-45 connectors.
Allure EC-Smart-Comfort and EC-Smart-Air communicating sensor series share
the same Subnet ID range: the same address cannot be assigned concurrently to
an Allure EC-Smart-Comfort communicating sensor series and to an Allure EC-
Smart-Air communicating sensor series.