Controller Installation and Maintenance Tasks with an Allure EC-Smart-Vue Sensor
Network Guide
99
5.
Press the down button
once to enter the GEN CFG submenu
6.
Press the Menu button
several times until SUBNET ID appears on the display. The
current controller's Subnet ID is shown.
7.
For commissioning purposes, use the up and down buttons
to set the controller's
Subnet ID to 1. Tip: Hold down either the up or down button to fast-advance the display
value. Otherwise use the up and down buttons to set the controller's Subnet ID to the
ComSensor block instance value programmed in the controller with EC-
gfx
Program.
8.
Press the Menu button
once to apply the value.
9.
Press and hold the Menu button
for 5 seconds to exit the configuration menu.
The Allure EC-Smart-Vue sensor can now be used to go from one ECB/ECL Series controller
to the next for commissioning purposes.
When the controller has been programmed, each connected Allure EC-Smart-Vue's Sensor
must be assigned a unique Subnet ID.
Commissioning Controllers
To commission a controller with a MAC Address DIP switch located on the faceplate or under
the cover (in the case of an ECB-103 or ECB-VAV Series controller - when equipped), first set
the DIP switch to 0 (all off - this is the factory default setting when the controller is shipped).
When using an Allure EC-Smart-Vue sensor for commissioning a controller (before code is
downloaded to the controller from EC-
gfx
Program), connect an Allure EC-Smart-Vue sensor
to the controller with its Subnet ID set to 1.
For ECB-VAV and ECL-VAV Series controllers, commissioning can be used to perform appli-
cation selection if needed. Applications are preloaded programs that enable the ECB-VAV and
ECL-VAV to control a typical VAV box. See the ECL-VAV or ECB-VAV Preloaded Application
User Guide for more Information.
OR
Screen Timeout: 30 seconds
OR
Screen Timeout: 30 seconds
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...