1.5 Chemical Risk
▲
WARNING
Lithium batteries are chemical risk if misoperated,
mishandled or abused.
1.6 Do’s
• Do protect terminals from short circuit before, during, and after installation
• Do wear electrically insulated gloves
• Do use electrically insulated tools
• Do wear eye protection
• Do wear safety toe boots / shoes
• Do handle battery carefully
• Do secure battery safely
• Do always assume battery terminals are energized
1.7 Do Not’s
• Do not lift or carry the battery during usage or operation
• Do not operate or store battery outside of operating limits
• Do not short circuit battery
• Do not puncture battery
• Do not expose battery to flames, or incinerate
• Do not open battery case or dissemble battery
• Do not wear rings, watches, bracelets or necklaces when handling or working near battery
• Do not drop or crush battery
• Do not lift battery by the terminal cables
• Do not vibrate battery
• Do not expose battery to water or other fluids
• Do not expose battery to direct sunlight
• Do not dispose of battery
• Do not connect with other types of batteries
• Do not expose battery to high temperatures
• Do not install with other battery types or brands
1.8 DC Motor Connection
Direct connection to DC motors without proper safety protection, motor controllers, and external motor voltage clamping
systems (such as high power anti-parallel diodes or braking resistor systems) may result in damage to the internal pack
protection system which may result in unsafe situations. Please consult Discover technical support before directly connecting any
motor loads.
1.9 Transportation
If the battery is not installed in equipment, it must be transported in the original package or equivalent.
Batteries are tested according to UN Handbook of Tests and Criteria, part III, sub section 38.3 (ST/SG/AC. 10/11/Rev.5). For
transport the batteries belong to category UN3480, Class 9, Packaging Group II.
2. OPERATING LIMITS
2.1 Battery Operating Limits
The battery should not be operated outside these operating limits.
Operating Limits
15-24-1000
15-36-1000
Discharge and Charge Current
40 A
25 A
Charge Voltage
27.2 V
40.8
Operating Voltage (Min / Max)
22.4 V / 29.6 V
33.6 V / 44.4 V
Charge Temperature (Min / Max)
0°C / 45°C (32°F / 113°F)
Discharge Temperature (Min / Max)
-20°C / 60°C (-4°F / 140°F)
Storage Temperature (Min / Max)
-20°C / 45°C (-4°F / 113°F)