7
discoverbattery.com
▲
NOTE!
All cable ends must be connected to battery terminals without
any washers between terminal bushings and cable ends.
Terminal burnout is caused by:
• Discharge currents exceeding allowable limits
• Improper cable installation
• Improper cable sizing
• Improper terminal torque
▲
NOTE!
Without exception, product experiencing terminal burn out
will not be warranted.
5.5 Parallel Battery Wiring
To ensure proper balancing and load sharing between parallel batteries refer to the wiring diagram below. Lithium batteries are
very sensitive to voltage and undersized battery cables will limit battery and system performance. The thickness (cross section) of
cable used should exceed the recommended minimum for the inverter charger installation whenever possible.
Five or more batteries in parallel should be installed using a busbar configuration. In a busbar configuration all battery cable sets
should be the same length regardless of the battery’s proximity to the busbar (or combiner box). Actual wiring requirements may
vary. Consult with the authority having local jurisdiction.
M8” bolt (supplied with battery)
Copper compression lug
Shrink-wrap to
color-code the cable
Terminal surface
Lock washer (supplied with battery)
Flat washer (supplied with battery)
Battery cable lug
Ensure nothing is between
the terminal surface and the
battery cable lug
Terminal hardware
IS NOT
bottomed out!
Terminal hardware
IS
bottomed out!
Washers
ARE NOT
compressed!
Washers
ARE NOT
compressed!
Terminal hardware
IS
bottomed out!
Terminal hardware
IS NOT
bottomed out!
LOAD / CHARGER
LOAD / CHARGER
LOAD / CHARGER
LOAD / CHARGER
CHARGER CHARGER
INSTALLATION USING BUSBAR
CHARGER
CHARGER
LOAD
LOAD
LOAD
LOAD
All parallel cables should be the same length.
All parallel cables should be the same length.
All parallel cables should be the same length.
All parallel cables should be the same length.
All cables should be the same length.
INSTALLATION USING CABLES