background image

EN-8

452237.66.54 · FD 9912

www.gdts.one

English

SI 35TUR

7.4.4 Hydraulic distribution system

The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the domestic hot water cylinder. A compact system is
used to simplify the installation process, so that a lot of different
components do not have to be installed individually. Further in-
formation can be found in the relevant installation instructions.

Compact manifold

The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.

Dual differential pressureless manifold

In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.

7.5 Electrical connection 

7.5.1 General

All electrical installation work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the 

installation and operating instructions, 

country-specific installation regulations (e.g. VDE 0100),

technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and

local conditions. 

To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is applied to controller terminals N1-J1 to N1-
J11; N1-J19; N1-J20; N1-J23 to N1-J26; N17-J1 to N17-J4;
N17-J9; N17-J10; N0-J2 to N0-J14 and the terminal strips X3
and X5.1. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be
destroyed.

7.5.2 Electrical installation work 

1) The 4-core electrical supply cable for the output section of

the heat pump is fed from the heat pump meter via the util-
ity company blocking contactor (if required) into the heat
pump.
Connection of the mains cable to the contact plate of the
heat pump via terminals X1: L1/L2/L3/PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping
for all external conductors must be installed in the power
supply for the heat pump (tripping current and characteris-
tic in compliance with the device information).

ATTENTION!

!!

Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).

2) The three-core supply cable for the heat pump manager

(heating controller N1) is fed into the heat pump.
Connection of the control cable to the contact plate of the
heat pump via terminal X2: L/N/PE. 
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The supply cable (L/N/PE~230 V, 50 Hz) for the heat pump
manager must have a continuous voltage. For this reason,
it should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, because
otherwise important protection functions could be lost
during a utility block.

3) The utility blocking contactor (K22) with 3 main contacts

(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied on-site.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to controller N1/J5-ID3.

CAUTION! Extra-low voltage!

4) The contactor (K20) for the immersion heater (E10) of

mono energy systems (HG 2) should be dimensioned ac-
cording to the radiator output and must be provided on-
site. It is controlled (230 V AC) from the heat pump man-
ager via terminals X2/N and contact N1/J13-NO4 on the
heat pump manager.

5) The contactor (K21) for the flange heater (E9) in the do-

mestic hot water cylinder should be dimensioned accord-
ing to the radiator output and must be provided on-site. It
is controlled (230 V AC) from the heat pump manager via
terminals X2/N and contact N1/J16-NO10.

6) The contactors mentioned above in points 3, 4 and 5 are

installed in the electrical distribution system. Mains cables
for installed heating systems must be designed and pro-
tected in accordance with the valid standards and regula-
tions.

7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is activated via the con-

tact N1-J13/NO5. Connection points for the pump are
coupling relays KM13/14 and X2/N.

9) The auxiliary circulating pump (M16) is activated via the

contact N1-J16/NO9. Connection points for the pump are
coupling relays KM16/14 and X2/N. 

Содержание SI 35TUR

Страница 1: ...rauchsanweisung Sole Wasser W rmepumpe f r Innenaufstellung Installation and Operating Instruction Brine to Water Heat Pump for Indoor Installation Instuctionsd installation et d utilisation Pompe cha...

Страница 2: ......

Страница 3: ...DE 5 7 2 Heizungsseitiger Anschluss DE 6 7 3 W rmequellenseitiger Anschluss DE 6 7 4 Temperaturf hler DE 7 7 5 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 9 8 1 Allgemein DE 9 8 2 Vorbereitung DE...

Страница 4: ...t von 7 5 minimal zul ssiger Wert f r Kupfer nicht unterschritten wird Eine Unterschreitung kann zur Zerst rung der W rmepumpe f hren ACHTUNG Im W rmequelleneintritt der W rmepumpe ist der beiliegende...

Страница 5: ...ne um 1 K h here Heizwassertemperatur stei gert den elektrischen Energieverbrauch um ca 2 5 Eine Nie dertemperaturheizung mit Vorlauftemperaturen zwischen 30 C und 50 C ist f r einen energiesparenden...

Страница 6: ...haltventil 4 Zubeh r 4 1 Anschlussflansche Durch den Einsatz von flachdichtenden Anschlussflanschen kann das Ger t optional auf Flanschanschluss umgestellt wer den 4 2 Fernbedienung Als Komforterweite...

Страница 7: ...muss in einem frostfreien und trockenen Raum auf einer ebenen glatten und waagerechten Fl che aufgestellt werden Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine ausreichende Schallabdi...

Страница 8: ...epumpe f hren Es wird empfohlen an der Heizwasserr cklaufseite des mon tierten hydraulischen 4 Wege Umschaltventil einen Schmutz f nger zu montieren Mindestheizwasserdurchsatz Der Mindestheizwasserdur...

Страница 9: ...tern T ren Abluft ffnungen Au enleuchten oder W rmepumpen anbringen zu keiner Jahreszeit direkter Sonneneinstrahlung ausset zen 7 4 3 Montage der Anlegef hler Die Montage der Anlegef hler ist nur notw...

Страница 10: ...teristik gem Ger teinformation ACHTUNG Rechtsdrehfeld beachten Bei falscher Verdrahtung wird das Anlaufen der W rmepumpe verhindert Ein entsprechender Warnhinweis wird im W rmepumpenmanager angezeigt...

Страница 11: ...Anlaufstrom von 12 A der elektronisch geregelten Umw lzpumpe nicht berschritten wird oder es liegt eine ausdr ckliche Freigabe des Pumpenherstellers vor ACHTUNG Es ist nicht zul ssig ber einen Relaisa...

Страница 12: ...Schmutzf nger zu montieren um den Verdampfer gegen Verunreinigungen zu sch tzen Einen Tag nach der Inbetriebnahme sollte das Filtersieb des Schmutzf ngers gereinigt werden Weitere Kontrollen sind je...

Страница 13: ...bei B 5 W55 kW 13 3 2 7 26 9 2 6 bei B0 W55 47 kW 15 3 3 0 30 3 2 9 bei B0 W45 40 kW 16 8 3 9 31 9 3 6 bei B0 W35 30 kW 18 4 5 1 33 7 4 6 4 3 K hlen Durchfluss freie Pressung Sole K hlwasser Mindestdu...

Страница 14: ...stungsf higkeit der Anlage nach EN 14511 F r wirtschaftliche und energetische Betrachtungen sind Bivalenzpunkt und Regelung zu ber cksichtigen Diese Angaben werden ausschlie lich mit sauberen W rme be...

Страница 15: ...gspegel innen au en LWA 58 dB 6 7 m h Stickoxidaussto NOx mg kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel...

Страница 16: ...eile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten Im...

Страница 17: ...5 7 1 General EN 5 7 2 Connection on heating side EN 6 7 3 Heat source connection EN 6 7 4 Temperature sensor EN 7 7 5 Electrical connection EN 8 8 Commissioning EN 9 8 1 General EN 9 8 2 Preparation...

Страница 18: ...r is complied with Failure to comply with this value can result in the heat pump being destroyed ATTENTION The supplied dirt trap must be inserted in the heat source inlet of the heat pump to protect...

Страница 19: ...Low temperature heating systems with flow temperatures between 30 C and 50 C are particularly well suited for energy efficient operation 2 Intended use of the heat pump 2 1 Area of application The bri...

Страница 20: ...valve 7 Filter dryer 8 Four way reversing valve 4 Accessories 4 1 Connection flange The device can optionally be switched to flange connection using the flat sealing connection flange 4 2 Remote contr...

Страница 21: ...ed in a frost free dry room on an even smooth and horizontal surface The entire base of the frame should lie directly on the floor to ensure an adequate soundproof seal If this is not the case additio...

Страница 22: ...dirt trap on the heating water return side of the mounted hydraulic 4 way reversing valve Minimum heating water flow rate The minimum heating water flow rate through the heat pump must be assured in a...

Страница 23: ...alcony Not in the vicinity of windows doors exhaust air vents ex ternal lighting or heat pumps Not to be exposed to direct sunlight at any time of year 7 4 3 Installing the strap on sensor It is only...

Страница 24: ...eat pump via terminals X1 L1 L2 L3 PE An all pole disconnecting device with a contact gap of at least 3 mm e g utility blocking contactor or power contac tor and an all pole circuit breaker with commo...

Страница 25: ...h starting currents which may shorten the service life of the heat pump manager A coupling relay must therefore be installed between the output of the heat pump manager and the electronically regulate...

Страница 26: ...source system ATTENTION The supplied dirt trap must be inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities The filter sieve of the dirt trap...

Страница 27: ...6 at B0 W55 47 kW 15 3 3 0 30 3 2 9 at B0 W45 40 kW 16 8 3 9 31 9 3 6 at B0 W35 30 kW 18 4 5 1 33 7 4 6 4 3 Cooling flow free compression Brine Cooling water Minimum flow rate m h Pa 8 0 61200 5 9 399...

Страница 28: ...of the economic and energy efficiency of the system the bivalence point and the regulation should be taken into consideration These figures are only achieved with clean heat exchangers Information on...

Страница 29: ...sions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not dete...

Страница 30: ...EN 14 452237 66 54 FD 9912 www gdts one English SI 35TUR...

Страница 31: ...5 7 1 G n ralit s FR 5 7 2 Raccordement c t chauffage FR 6 7 3 Raccordement c t source de chaleur FR 6 7 4 Sonde de temp rature FR 7 7 5 Branchements lectriques FR 8 8 Mise en service FR 9 8 1 G n ra...

Страница 32: ...e pH soit 7 5 valeur minimale admissible pour le cuivre Si cette valeur n est pas atteinte la pompe chaleur peut tre d truite ATTENTION Monter dans l entr e de la source de chaleur de la pompe chaleur...

Страница 33: ...on de la consommation d nergie lectrique Un chauffage basse temp rature avec des temp ra tures d part comprises entre 30 C et 50 C convient un fonc tionnement conome en nergie 2 Usage pr vu pour la po...

Страница 34: ...endeur 7 Filtre d shydrateur 8 Vanne d inversion 4 voies 4 Accessoires 4 1 Brides de raccordement Les brides de raccordement joint plat permettent de proc der si n cessaire un raccordement par bridage...

Страница 35: ...local sec l abri du gel sur une surface plane lisse et horizon tale Le ch ssis de la pompe chaleur doit tre bien en contact avec le sol sur toute sa circonf rence afin de garantir une isola tion sono...

Страница 36: ...d truite Il est recommand de monter un collecteur d impuret s c t retour d eau de chauffage de la vanne hydraulique d inversion 4 voies install e D bit minimum d eau de chauffage Le d bit minimum d ea...

Страница 37: ...pas l installer proximit de fen tres de portes d ou vertures d a ration de dispositifs d clairage ext rieur ou de pompes chaleur Ne pas l exposer aux rayons directs du soleil quelle que soit la saison...

Страница 38: ...p ex contacteur de blo cage de la soci t d lectricit ou contacteur de puissance ainsi qu un coupe circuit automatique omnipolaire avec d clenchement simultan de tous les conducteurs ext rieurs courant...

Страница 39: ...tre la sortie du gestionnaire de pompe chaleur et le circulateur r gulation lectronique Ceci n est pas n cessaire lorsque le courant de service admis sible de 2 A et un courant de d marrage maximal de...

Страница 40: ...u collecteur d impure t s un jour apr s la mise en service D finir la p riodicit des contr les suivants en fonction de l encrassement Si aucune impuret n est plus signaler on pourra d monter le tamis...

Страница 41: ...5 kW 13 3 2 7 26 9 2 6 pour B0 W55 47 kW 15 3 3 0 30 3 2 9 pour B0 W45 40 kW 16 8 3 9 31 9 3 6 pour B0 W35 30 kW 18 4 5 1 33 7 4 6 4 3 Rafra chissement d bit compression libre eau glycol e eau de rafr...

Страница 42: ...llation selon EN 14511 Lors de consid rations conomiques et nerg tiques le point de bivalence et la r gulation doivent tre pris en compte Ces donn es sont atteintes uniquement avec des changeurs therm...

Страница 43: ...mation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Pour les dispositifs...

Страница 44: ...FR 14 452237 66 54 FD 9912 www gdts one Fran ais SI 35TUR...

Страница 45: ...gram Sch ma d int gration A VIII 3 1 Reversible W rmepumpenanlage mit 3 Heizkreisen Warmwasserbereitung und Schwimmbadbereitung Reversible heat pump system with three heating circuits domestic hot wat...

Страница 46: ...912 www gdts one Anhang Appendix Annexes SI 35TUR 1 Ma bild Dimension drawing Sch ma cot 1 1 Ma bild Dimension drawing Sch ma cot SI 35TUR 1 5 1 6 1 1 1 2 3 1 3 2 0 167 189 364 595 0 448 565 569 25 76...

Страница 47: ...etour circuit de chauffage retour circuit de rafra chissement Entr e dans la pompe chaleur G 1 1 2 AG 1 5 W rmequelle Eingang in W rmepumpe G 1 1 2 AG Heat source Input into heat pump G 1 1 2 AG Sourc...

Страница 48: ...inlet temperature in C Temp rature d entr e d eau glycol e en C Leistungszahl incl Pumpenleistungsanteil Coefficient of performance incl power input to pump Coefficient de performance y compris part d...

Страница 49: ...Leistungsaufnahme in kW incl Pumpenleistungsanteil Power consumption in kW incl power input to pump Consommation de puissance en kW y compris part de consommation de la pompe Druckverlust in Pa Press...

Страница 50: ...e des seuils d utilisation chauffage 0 5 10 15 20 25 30 35 40 45 50 55 60 65 10 5 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperature C Temp rature d eau chauffage C W rmequelleneintri...

Страница 51: ...agramme des seuils d utilisation rafra chissement 0 5 10 15 20 25 0 5 10 15 20 25 30 35 K hlwassertemperatur C Cooling water temperature C Temp rature d eau de rafra chissement C W rmesenkeneintrittst...

Страница 52: ...und Schwimmbadbereitung Reversible heat pump system with three heating circuits domestic hot water preparation and swimming pool water Installation r versible de pompe chaleur avec trois circuits de c...

Страница 53: ...eisen Warmwasserbereitung und Schwimmbadbereitung Electrical circuit diagram for reversible heat pump system with three heating circuits domestic hot water preparation and swimming pool water Sch ma l...

Страница 54: ...A X 452237 66 54 FD 9912 www gdts one Anhang Appendix Annexes SI 35TUR 3 3 Elektroschema K hlmodul Electrical circuit diagram cooling module Sch ma lectrique module de rafra chissement...

Страница 55: ...au chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 2 l Gaskessel Oil gas boiler Chaudi re fuel gaz M11 Prim rumw lzpumpe Primary circulating pump Cir...

Страница 56: ...erkl rung Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous...

Страница 57: ...www gdts one 452237 66 54 FD 9912 A XIII SI 35TUR Anhang Appendix Annexes...

Страница 58: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Отзывы: