EVO Control Panel
19
8
Alarm Options
8.1 Bell/alarm Output
(default =
only option [1] enabled
) When an alarm condition is detected in
a partition, the control panel can trigger the on-board
BELL
output enabling
any bells or sirens connected to it. In section
[3032]
enable the option to
enable the bell output in the desired partition (off = disabled):
8.2 Bell Cut-off Timer
(default =
004
) After an audible alarm, the bell or siren will stop once the
partition is disarmed or when the Bell Cut-Off Timer has elapsed. Enter any
value between 001 and 255 minutes:
8.2.1 No Bell Cut-Off on Fire Alarm
S
ECTION
[3030]: O
PTION
[2]
(default =
disabled
) The control panel can disable the Bell Cut-Off Timers
when alarms are generated from zones defined as Standard or Delayed
Fire Zones (see
BELL
output will remain
enabled until a user disarms the partition in alarm.
8.2.2 Recycle Alarm Rate
(default =
000
) The control panel re-verifies the zone status during an alarm
at a programmed rate once the Bell Cut-Off Timer and the Recycle Delay
elapse. If open zones remain, the control panel will regenerate the alarm.
Enter the number of times from 001 to 255 (000 = no limit) in one armed
period that the control panel will re-verify the zone status:
8.2.3 Recycle Delay
(default =
000
) The Recycle Delay is the amount of time the control panel
will wait after the Bell Cut-off occurs before re-verifying the zone status.
Program the Recycle Delay from 001 to 255 minutes (000 = disabled):
8.3 Wireless Transmitter Supervision Options
S
ECTION
[3034]: O
PTIONS
[1]
AND
[2]
When the control panel detects a Supervision Loss, the control panel can
generate an alarm and/or trouble, unless the Wireless Transmitter
Supervision Option is disabled.
The Supervision feature must be enabled in the Magellan Wireless
System (MG-RTX3) for this feature to function.
8.3.1 Supervision Bypass Options
S
ECTION
[3034]: O
PTION
[3]
(default =
disabled
) When enabled in section
[3034]
, the Wireless
Transmitter Supervision Options will follow the zone's bypass definition.
The control panel will not perform any action if a supervision loss occurs on
a bypassed zone. When disabled, it will ignore the bypass definition and will
follow the option set in
.
8.4 Police Code Timer
(default =
000
) If an alarm condition occurs on a zone, the control panel
generates an alarm and triggers the Police Code Timer. The Police Code
programmed in
[3934]
will only be sent if one of the following conditions
occurs during the delay:
1.
An alarm occurs on another zone.
2.
The zone in alarm restores and reoccurs.
Key in the desired 3-digit delay value (001 to 255 minutes, 000 = disabled)
into the section corresponding to the desired partition:
on page 12 to set it up so that a police code is
only generated on Zone Crossing.
8.5 Tamper Recognition Options
S
ECTION
[3034]: O
PTIONS
[5]
AND
[6]
When the control panel detects a tamper or wire fault on a zone or on an
expansion module, the control panel can generate an alarm and/or trouble,
as shown in the table below.
Partition 1: Option
[1]
Partition 5: Option
[5]
Partition 2: Option
[2]
Partition 6: Option
[6]
Partition 3: Option
[3]
Partition 7: Option
[7]
Partition 4: Option
[4]
Partition 8: Option
[8]
Partition 1:
[3113]
Partition 3:
[3313]
Partition 5:
[3513]
Partition 7:
[3713]
Partition 2:
[3213]
Partition 4:
[3413]
Partition 6:
[3613]
Partition 8:
[3813]
Partition 1:
[3117]
Partition 3:
[3317]
Partition 5:
[3517]
Partition 7:
[3717]
Partition 2:
[3217]
Partition 4:
[3417]
Partition 6:
[3617]
Partition 8:
[3817]
Partition 1:
[3116]
Partition 3:
[3316]
Partition 5:
[3516]
Partition 7:
[3716]
Partition 2:
[3216]
Partition 4:
[3416]
Partition 6:
[3616]
Partition 8:
[3816]
[1] [2] Description
OFF OFF
Disabled (default):
Displays zone open on the keypads, but will not generate an
alarm or trouble.
Not permitted on UL systems.
OFF ON
Generates Trouble Only (when armed or disarmed):
The control panel displays
Zone Fault
in the Trouble Display
and transmits the defined report code (see
22).
ON OFF
When disarmed: Generates Trouble Only
The control panel displays
Zone Fault
in the Trouble Display
and transmits the defined report code (see
22).
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see
ON
ON
When disarmed: Generates Audible Alarm
The control panel displays
Zone Fault
in the Trouble Display,
transmits the defined report code (see
and generates an audible alarm.
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see
Partition 1:
[3118]
Partition 3:
[3318]
Partition 5:
[3518]
Partition 7:
[3718]
Partition 2:
[3218]
Partition 4:
[3418]
Partition 6:
[3618]
Partition 8:
[3818]
[5] [6] Description
OFF OFF
Disabled (default):
Displays zone open on the keypads, but will not generate an
alarm or trouble.
Not permitted on UL systems.
OFF ON
Generates Trouble Only (when armed or disarmed):
The control panel displays
Zone Fault
in the Trouble Display and
transmits the defined report code (see
ON OFF
When disarmed: Generates Trouble Only
The control panel displays
Zone Fault
in the Trouble Display and
transmits the defined report code (see
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see
ON
ON
When disarmed: Generates Audible Alarm
The control panel displays
Zone Fault
in the Trouble Display,
transmits the defined report code (see
and generates an audible alarm.
When armed: Follows Zone Alarm Type
The control panel follows the zone’s alarm type (see