ME 200 E ENG
- 29 -
The control unit will cyclically propose the values to be set for each channel, at
the end the settings of the common values of the control unit will follow
C: PROTECTION OF FAN BEARINGS,
default 1, C=0 not active, C=1 fan ignition
once a day 5 min, C=2 fan ignition once a
week 5 min
At the end of the programming cycle, the control unit performs the test on all
the light sectors and positions itself in the main menu displaying the maximum
measured temperature and the relative channel.
For safety reasons, the time required for programming is in any case checked.
Over one minute from the start of the programming phase, the same is
interrupted and not saved (therefore the previously set parameters remain
active) after which it returns to automatic display mode.
IP ADDRESS CONFIGURATION
Allows to configure the IP address on the device. The subnet mask is fixed
and is 255.255.255.0. The gateway is fixed and is 192.168.1.1
First IP address number, default 192
Second IP address number, default 168
Third IP address nunmer, default 1
Fourth IP address number, default 205
THERMOMETRIC PROBES DIAGNOSTICS
PROBE INTERRUPTED: FAULT relay switching,
display flashing, letters "ICF" display with relative
channel number and FAULT led lighting.
PROBE IN SHORT CIRCUIT: FAULT relay
switching, display flashing, letters "SCF" display
with relative channel number and LED diode
lighting.