DeZURIK
APCO AVV-140/150 with CSV-1600 Option Slow Closing
Air/Vacuum Valves
D12021
Page 12
June 2019
Troubleshooting
Condition
Possible Cause
Corrective Action
Valve leaks at flange joint.
Loose flange bolting.
Tighten flange bolting.
Blown flange gasket.
Replace flange gasket.
Misalignment or damage to field
piping and supports.
Adjust misalignment or repair
piping or supports.
Damaged flange face/s or
improper flange connections.
Repair flange, replace valve
body or adjust flange
connections.
Valve leaks out of outlet port.
Dirty seat and/or float.
Clean seat and/or float.
Worn seat and/or float.
Replace seat and/or float.
Line pressure is under 10 psi
(70KPa).
Replace seat with softer seat.
Float linkage is dirty.
Clean float linkage.