Vstart
0-150% Vref
The PFP mode is enable when grid
voltage is greater than Vstart
0-150% Vref
The PFP mode is disable when grid voltage
is less than Vstop
0-110% Pn
Power value at point (PF1,P1) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (PF1,P1) on the PF(P)
Curve
0-110% Pn
Power value at point (PF2,P2) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (P2,PF2) on the PF(P)
Curve
0-110% Pn
Power value at point (P3,PF3) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (P3,PF3) on the PF(P)
Curve
0-110% Pn
Power value at point (P4,PF4) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (P4,PF4) on the PF(P)
Curve
0-110% Pn
Power value at point (P5,PF5) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (P5,PF5) on the PF(P)
Curve
0-110% Pn
Power value at point (P6,PF6) on the PF(P)
Curve
0.8 leading - 0.8 lagging
PF value at point (P6,PF6) on the PF(P)
Curve
The time of the PFF Curve in seconds
(time to accomplish a change of 95%).
Vstop
P1
P2
P3
PF1
PF2
PF3
P4
PF4
P5
PF5
P6
PF6
RMpTime
Parameter
Range
Description
0-1000s
- 53 -
"PF(P)" Mode Parameters Explanation