17
-
5.4 Max. over current protec�on device
In order to protect the inverter AC connec�on, it is recommended to install a circuit breaker to
prevent overcurrent. See table 5.3 below.
Rated output
voltage(V)
Inverter
Rated output
current(A)
Current for protection
device(A)
SUN-6KK-G03-LV
127
15.7
30
Table 5.3 Recommended current protector specifica�ons
5.5 Inverter monitoring connec�on
Inverter has the func�on of wireless remote monitoring. The inverter with Wi-Fi func�on is
equipped with Wi-Fi Plug to connect the inverter and network. Wi-Fi Plug's opera�on,
installa�on, Internet access, APP downloading and other processes are detailed in the
instruc�ons.
PC
Router
WIFI
GPRS
Web Server
Phone
Pic 5.12 Internet monitoring solu�on