- 14 -
The AC output connector is divided into three parts: matching socket, sleeve and sealing-
sleeve, as shown in picture 5.7, the steps are as follows:
Step 1: Remove the cable sealing ring and sleeve in sequence from the AC connector.
Step 2: Use strippers to strip the protec�ve sheath and insula�on layer of the AC cable to the
right length, as shown in Picture 5.8.
Step 3: Insert the cable (L1, L2, L3, N
,
PE) into the sealing sleeve.
Step 4: Use the hexagon screwdriver, loosen the bolts of the socket in turn, and insert each
cable core into the corresponding jack, and set each screw. The connec�on hole of AC
connec�on terminal labeling is shown in Picture 5.9.
Warning:
Be careful to dis�nguish the L1, L2,L3,N and PE of the AC cables.
1. Matching socket 2.Sleeve 3.Sealing core 4.Sealing nut
Pic 5.7 AC connector structure
Pic 5.8 Strip AC cable
8~15mm
40mm
1
2
3
4