- 28-
Safety Hint:
While the u�lity power is nega�ve and inverter has no output power, that means
the orienta�on of the current sensor is wrong, please turn off the inverter and
change orienta�on of the current sensor.
(when using SUN limiter, the arrow of current sensor points to the load)
High Temperature Hazard:
When using SUN limiter, the current sensor of limiter func�on needs to be
clamped on the fire line of the grid connected to the inverter, otherwise inverter
cannot able to normal operate.
7.5 Notes while using zero export func�on
For your safety and the opera�on of limiter func�on of the inverter, we put forward the
following sugges�ons and precau�ons:
Warning:
Under zero export mode we strongly recommend that the two PV arrays are
formed by the same number of PV panels of the same size, which will make the
inverter more responsive to limit the power.
7.6 How to browse the load power of your PV grid-�e plant on monitoring pla�orm?
If you want to browse load power of the system and how much energy (KWH) does it export to
grid
(
inverter output power is used to power the load firstly and then the surplus energy will
feed into grid
)
. You also need to connect the meter according to above diagram. A�er the
connec�on completed successfully, the inverter will show the load power on the LCD.
But please
don’t setup “Meter ON”
. Also, you will be able to browse the load power on the monitoring
pla�orm. The plant se�ng method as below descrip�on.
Firstly, go to the solarman pla�orm(h�ps://pro.solarmanpv.com, this link is for solarman
distributor account; or h�ps://home.solarmanpv.com, this link is for solarman end user
account;) plant home page and click “edit”