Hybrid Inverter

User Manual

R

SUN-8K-SG04LP3-EU

SUN-6K-SG04LP3-EU

SUN-5K-SG04LP3-EU

SUN-10K-SG04LP3-EU

SUN-12K-SG04LP3-EU

Содержание SUN-10K-SG04LP3

Страница 1: ...Hybrid Inverter User Manual R SUN 8K SG04LP3 EU SUN 6K SG04LP3 EU SUN 5K SG04LP3 EU SUN 10K SG04LP3 EU SUN 12K SG04LP3 EU ...

Страница 2: ... 11 Typical application diagram of diesel generator 3 10 Wiring diagram 3 12 phase parallel connection diagram 6 Mode 37 38 5 6 Battery Setup Menu 5 7 System Work Mode Setup Menu 5 8 Grid Setup Menu 5 9 Generator Port Use Setup Menu 5 10 Advanced Function Setup Menu 5 11 Device Info Setup Menu 4 OPERATION 4 1 Power ON OFF 4 2 Operation and Display Panel 5 LCD Display Icons 5 1 Main Screen 5 2 Sola...

Страница 3: ...DC terminals Please refer to Installa on sec on of this manual for the details Grounding instruc ons this inverter should be connected to a permanent grounded wiring system Be sure to comply with local requirements and regula on to install this inverter Never cause AC output and DC input short circuited Do not connect to the mains when DC input short circuits 2 Product Introduc on This is a mul fu...

Страница 4: ...ons 5 DC switch 4 Power on off bu on 6 Parallel port 7 Meter 485 port 8 Ba ery input connectors 9 Func on port 10 ModeBUS port 11 BMS port 12 PV input with two MPPT 13 Grid 15 Generator input 14 Load 16 WiFi Interface 1 02 2 3 4 5 8 9 12 13 14 15 16 7 6 10 11 GRID LOAD GEN ...

Страница 5: ... 03 2 2 Product Size Inverter Size Moun ng bracket 363 ...

Страница 6: ...rid Suppor ng WIFI monitoring and build in 2 strings for 1 MPP tracker 1 string for 1 MPP tracker Smart se able three stages MPPT charging for op mized ba ery performance Time of use func on Smart Load Func on 2 4 Basic System Architecture The following illustra on shows basic applica on of this inverter It also includes following devices to have a Complete running system Generator or U lity PV mo...

Страница 7: ...have received the items in the following package Wall moun ng bracket x1 Hybrid inverter x1 Parallel communica on cable x1 L type Hexagon wrench x1 Stainless steel an collision bolt M8 80 x4 User manual User manual x1 Ba ery temperature sensor x1 Wi Fi Plug op onal x1 Sensor Clamp x 3 Meter op onal x 1 Three Phase Smart Meter SET ESC ...

Страница 8: ... the television Antenna or antenna cable Not higher than al tude of about 2000 meters above sea level Not in environment of precipita on or humidity 95 Considering the following points before selec ng where to install Please select a ver cal wall with load bearing capacity for installa on suitable for installa on on concrete or other non flammable surfaces installa on is shown below Install this in...

Страница 9: ...e careful when li ing out from the package Choose the recommend drill head as shown in below pic to drill 4 holes on the wall 52 60mm deep 1 Use a proper hammer to fit the expansion bolt into the holes 2 Carry the inverter and holding it make sure the hanger aim at the expansion bolt fix the inverter on the wall 3 Fasten the screw head of the expansion bolt to finish the moun ng 500mm 500mm Inverter ...

Страница 10: ... ery and the inverter In some applica ons switching devices may not be required but over current protectors are s ll required Refer to the typical amperage in the table below for the required fuse or circuit breaker size Model 8Kw 6Kw 5Kw Wire Size Cable mm 1AWG 1AWG 2AWG 2 40 40 35 Torque value max 24 5Nm 24 5Nm 24 5Nm 10Kw 1 0AWG 60 24 5Nm 12Kw 1 0AWG 60 24 5Nm ...

Страница 11: ...y with a suitable cable is important for safe and efficient opera on of the system To reduce the risk of injury refer to Chart 3 2 for recommended cables All wiring must be performed by a professional person 3 In case of children touch or insects go into the inverter Please make sure the inverter connector is fasten to waterproof posi on by twist it clockwise Before making the final DC connec on or c...

Страница 12: ... the GEN signal is ac ve the open contact GS will switch on no voltage output G valve 3 4 reserved Grid_Ry 5 6 RSD 7 8 When ba ery is connected and the inverter is in ON status it will provide 12Vdc Parallel A Parallel communica on port 1 CAN interface Parallel B Parallel communica on port 2 CAN interface Meter_485 forenergymeter communica on ModeBUS Reserved BMS BMS port for ba ery communica on C...

Страница 13: ...1 2 Temp CT 11 3 3 3 Temperature sensor connec on for lead acid ba ery ...

Страница 14: ...ure the inverter can be securely disconnected during maintenance and fully protected from over current The recommended of AC breaker for the load port is 20A for 8kw 32A for 10kw and 32A for 12KW The recommended of AC breaker for the grid port is 63A for 8kw 63A for 10kw and 63A for 12KW All wiring must be performed by a qualified personnel It is very important for system safety and efficient opera o...

Страница 15: ... off output to protect your appliance but some mes it s ll causes internal damage to the air condi oner Before connec ng to PV modules please install a separately DC circuit breaker between inverter and PV modules It is very important for system safety and efficient opera on to use appropriate cable for PV module connec on To reduce risk of injury please use the proper recommended cable size as below...

Страница 16: ...to the inverter Safety Hint Please don t connect PV array posi ve or nega ve pole to the ground it could cause serious damages to the inverter Safety Hint Before connec ng inverter please make sure the PV array open circuit voltage is within the 1000V of the inverter Safety Hint Before connec on please make sure the polarity of the output voltage of PV array matches the DC and DC symbols Pic 5 1 D...

Страница 17: ...are listed as follows a Strip off the DC wire about 7mm disassemble the connector cap nut see picture 5 3 b Crimping metal terminals with crimping pliers as shown in picture 5 4 c Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector as shown in picture 5 5 Pic 3 3 Disassemble the connector cap nut 7mm 7mm Pic 3 4 Crimp the contact pin to ...

Страница 18: ...e panel will generate voltage high voltage in series may cause danger to life Therefore before connec ng the DC input line the solar panel needs to be blocked by the opaque material and the DC switch should be OFF otherwise the high voltage of the inverter may lead to life threatening condi ons Warning Use the DC power connector of the accessories Do not interconnect the connectors of different man...

Страница 19: ...CT2 CT3 17 Inverter Load GEN Grid N R S T PE N R S T PE N R S T PE N R S T PE CT Arrow pointing to inverter The second side of the CT only needs to connect the master inverter Note when the reading of the load power on the LCD is not correct please reverse the CT arrow ...

Страница 20: ... 10 CHINT meter Three Phase Smart Meter SET ESC 1 7 4 10 25 24 3 9 6 10 RS 485 CHNT DTSU666 3 6 9 10 1 4 7 10 R S T Grid Load GEN Grid N R S T PE N R S T PE N R S T PE Inverter N L R R S S T T N N Parallel_A Parallel_B Meter 485 port RS485A N R S T PE RS485B Grid Eastron meter Eastron SDM630 Modbus V2 RS 485 RS485B RS485A B A G 5 6 7 8 1 2 3 4 1 2 3 4 R S T 5 6 7 8 GND Eastron 5 6 7 8 R S T Eastro...

Страница 21: ...tra ons of the Wi Fi Plug 3 7 Earth Connec on mandatory Ground cable shall be connected to ground plate on grid side this prevents electric shock if the original protec ve conductor fails Note When the inverter is in the off grid state the N line needs to be connected to the earth ...

Страница 22: ...PE S T PE T R N S PE T T AC Breaker Hybrid Inverter CT1 CT2 CT3 RCD Home Loads RCD E BAR N BAR E N Link Grid Battery BMS DC Breaker PV DC Breaker This diagram is an example for an applica on that neutral connects with the PE in a distribu on box For countries such as Australia New Zealand South Africa etc please follow local wiring regula ons ...

Страница 23: ...N 6K SG EU 200A DC breaker SUN 8K SG EU 250A DC breaker SUN 10K SG EU 300A DC breaker SUN 12K SG EU 300A DC breaker AC Breaker for backup load SUN 5K SG EU 16A AC breaker SUN 6K SG EU 16A AC breaker SUN 8K SG EU 20A AC breaker SUN 10K SG EU 32A AC breaker SUN 12K SG EU 32A AC breaker AC Breaker for grid SUN 5K SG EU 63A AC breaker SUN 6K SG EU 63A AC breaker SUN 8K SG EU 63A AC breaker SUN 10K SG ...

Страница 24: ...erator Remotely control signal line AC Breaker SUN 10K SG EU 300A DC breaker SUN 12K SG EU 300A DC breaker SUN 5K SG EU 150A DC breaker SUN 6K SG EU 200A DC breaker SUN 8K SG EU 250A DC breaker DC Breaker for battery SUN 10K SG EU 32A AC breaker SUN 8K SG EU 20A AC breaker SUN 6K SG EU 16A AC breaker SUN 5K SG EU 16A AC breaker SUN 12K SG EU 32A AC breaker AC Breaker for backup load SUN 5K SG EU 6...

Страница 25: ... Inverter Load GEN Grid N R S T PE N R S T PEN R S T PE Load GEN Grid N R S T PE N R S T PEN R S T PE Load GEN Grid N R S T PE N R S T PEN R S T PE Battery pack Home Load R S T N PE R S T N PE CT Arrow pointing to inverter DC Breaker for battery SUN 5K SG EU 150A DC breaker SUN 6K SG EU 200A DC breaker SUN 8K SG EU 250A DC breaker SUN 10K SG EU 300A DC breaker SUN 12K SG EU 300A DC breaker AC Brea...

Страница 26: ...and Display Panel The opera on and display panel shown in below chart is on the front panel of the inverter It includes four indicators four func on keys and a LCD display indica ng the opera ng status and input output power informa on Chart 4 1 LED indicators LED Indicator DC AC Normal Alarm Green led solid light Green led solid light Green led solid light Red led solid light PV Connec on normal ...

Страница 27: ... bu on you can enter into the system setup screen which including Basic Setup Ba ery Setup Grid Setup System Work Mode Generator port use Advanced func on and Li Ba info 4 The main screen showing the info including Solar Grid Load and Ba ery Its also displaying the energy flow direc on by arrow When the power is approximate to high level the color on the panels will changing from green to red so sy...

Страница 28: ...Main Screen Solar Page Solar Graph Grid Graph BMS Page Load Graph Battery Setting System Work Mode Grid Setting Gen Port Use Basic Setting Advanced Function Device info Grid Page Inverter Page Battery Page Load Page System Setup 26 ...

Страница 29: ...d Battery PV1 PV2 Grid Inverter Today 0 5 KWH Total 1 60 KWH L1 220V P1 19W L2 220V P2 18W L3 220V P3 18W Load Energy This is Back up Load detail page Press the Energy bu on will enter into the power curve page Back up Power Voltage Power for each Phase Back up consump on for Day and Total This is Grid detail page Press the Energy bu on will enter into the power curve page Status Power Frequency B...

Страница 30: ...ear Total System Grid Power Total CANCEL Day Month Year Total Mean Voltage 50 34V Charging Voltage 53 2V Total Current 55 00A Discharging Voltage 47 0V Mean Temp 23 5C Charging current 50A Total SOC 38 Discharging current 25A Sum Data Details Data Dump Energy 57Ah Li BMS Volt 1 2 3 50 38V 19 70A 30 6C 52 0 26 0Ah 0 0V 0 0A 0 0 0 50 33V 19 10A 31 0C 51 0 25 5Ah 53 2V 25 0A 0 0 0 50 30V 16 90A 30 2C...

Страница 31: ...7 Factory Reset Reset all parameters of the inverter Lock out all changes Enable this menu for se ng parameters that require locking and cannot be set up Before performing a successful factory reset and locking the systems to keep all changes you need to type in a password to enable the se ng The password for factory se ngs is 9999 and for lock out is 7777 This is System Setup page Factory Reset P...

Страница 32: ...he Current that the Grid charges the Ba ery Grid Charge It indicates that the grid charges the ba ery This is Grid Charge you need select Batt Mode Lithium Use Batt V Battery Setting Activate Battery Max A Charge Batt Capacity Max A Discharge 40A 40A 400Ah Batt Mode Use Batt No Batt Ba ery capacity it tells Deye hybrid inverter to know your ba ery bank size Use Ba V Use Ba ery Voltage for all the ...

Страница 33: ...low this value Low Ba 20 It indicates the inverter will alarm if the SOC below this value Restart 40 Ba ery voltage at 40 AC output will resume This page tells generator output voltage frequency power And how much energy is used from generator Power 6000W Today 10 KWH Total 10 KWH Generator V_L1 230V V_L2 230V V_L3 230V P_L1 2KW P_L2 2KW P_L3 2KW There are 3 stages of charging the Ba ery This is f...

Страница 34: ... the load is as follows 1 Solar Panels 2 Grid 3 Ba eries un l programable discharge is reached Zero Export To Load Hybrid inverter will only provide power to the backup load connected The hybrid inverter will neither provide power to the home load nor sell power to grid The built in CT will detect power flowing back to the grid and will reduce the power of the inverter only to supply the local load...

Страница 35: ...ches 40 During 18 00 01 00 when ba ery SOC is higher than 35 hybrid inverter will discharge the ba ery un l the SOC reaches 35 Time Of Use Time System Work Mode Batt Grid Charge Gen 01 00 05 00 08 00 10 00 15 00 18 00 5 00 8 00 10 00 15 00 18 00 01 00 Power 80 40 40 80 40 35 Work Mode2 For example Solar Sell Solar sell is for Zero export to load or Zero export to CT when this item is ac ve the sur...

Страница 36: ...ng L HVRT L HFRT HV2 0 0V HV1 0 0V LV1 0 0V LV2 0 0V LV3 0 0V 0 16S 0 16S 0 16S 0 16S 0 16S HF2 0 00HZ HF1 0 00HZ LF1 0 00HZ LF2 0 00HZ 0 16S 0 16S 0 16S 0 16S Grid Set4 Please select the correct Grid Mode in your local area If you are not sure please choose General Standard Please select the correct Grid Type in your local area otherwise the machine will not work or be damaged Phase type When the...

Страница 37: ... Ba Ba ery SOC at which the Smart load will switch on simultaneously and then the Smart load will switch on On Grid always on When click on Grid always on the smart load will switch on when the grid is present Micro Inv Input To use the Generator input port as a micro inverter on grid inverter input AC coupled this feature will also work with Grid Tied inverters Micro Inv Input OFF when the ba ery...

Страница 38: ... it the inverter will provide the redundant part to ensure that the generator will not overload DRM For AS4777 standard Backup Delay Reserved BMS_Err_Stop When it is ac ve if the ba ery BMS failed to communicate with inverter the inverter will stop working and report fault Signal island mode Reserved Ex_Meter For CT when using zero export to CT mode the hybrid inverter can select EX_Meter For CT f...

Страница 39: ... 0 0 4 5 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00V 0 00A 0 0C 0 0 0 0Ah 0 0V 0 0A 0 0 0 0 00...

Страница 40: ... cannot and can only legally exclude all liability within a limited scope 38 The 1st priority power of the system is always the PV power then 2nd and 3rd priority power will be the ba ery bank or grid according to the se ngs The last power backup will be the Generator if it is available Grid Backup Load On Grid Home Load Battery Solar CT AC cable DC cable Smart Load Mode III With Smart Load Grid B...

Страница 41: ...inute and then turn on the DC AC switch 6 Seek help from us if can not go back to normal state AC side over current fault 1 Please check whether the backup load power and common load power are within the range 2 Restart and check whether it is in normal 3 Seek help from us if can not go back to normal state Leakage current fault 1 Check the PV side cable ground connection 2 Restart the system 2 3 ...

Страница 42: ...are firmly and correctly connected 3 Seek help from us if can not go back to normal state F29 Parallel CAN Bus fault 1 When in parallel mode check the parallel communication cable connection and hybrid inverter communication address setting 2 During the parallel system startup period inverters will report F29 But when all inverters are in ON status it will disappear automatically 3 If the fault st...

Страница 43: ...ommunication between hybrid inverter and battery BMS disconnected when BMS_Err Stop is active 2 if don t want to see this happen you can disable BMS_Err Stop item on the LCD 3 If the fault still exists please contact us for help F62 DRMs0_stop F34 AC Overcurrent fault F63 ARC fault F64 Heat sink high temperaturefailure 1 ARC fault detection is only for US market 2 Check PV module cable connection ...

Страница 44: ...e to the following reasons Damage during transporta on of equipment Damage caused by incorrect installa on or commissioning Damage caused by failure to comply with opera on instruc ons installa on instruc ons or maintenance instruc ons Damage caused by a empts to modify alter or repair products Damage caused by incorrect use or opera on Damage caused by insufficient ven la on of equipment Damage cau...

Страница 45: ...T Range V Start up Voltage V PV Input Current A No of MPPT Trackers No of Strings Per MPPT Tracker AC Output Data 2 mes of rated power 10 S Lead acid or Li lon 40 60V 3 Stages Equaliza on yes Self adap on to BMS 550V 160V 800V 200V 650V 160V 2 50A 11000 22 7 21 7A SUN 10K SG04LP3 210A 210A 13000W 26A 13A 2 1 10000 15 2 14 5A 34A 17A 13 6 13A SUN 6K SG04LP3 150A 7800W 1 1 9 1 8 7A 150A 13A 13A 17A ...

Страница 46: ...d Regula on IEC62109 1 2 EN61000 6 1 EN61000 6 2 EN61000 6 3 EN61000 6 4 EMC Safety Regula on General Data Protec on Degree Opera ng Temperature Rande Cooling Noise dB Communica on with BMS Weight kg Size mm Installa on Style Warranty 45 60 45 Dera ng 45 dB A Smart cooling RS485 CAN 33 6 422W 702H 281D IP65 5 years Wall mounted ...

Страница 47: ... 9 Appendix I 1 No 485_B RS485 Pin 2 485_A 3 4 CAN H 5 CAN L 6 GND_485 7 485_A 8 485_B 1 No 2 3 4 5 6 7 8 METER 485_B Meter 485 Pin METER 485_A COM GND COM GND METER 485_A METER 485_B 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 BMS Port Meter 485 Port 1 2 3 4 5 6 7 8 87 65 43 21 87 65 43 21 ...

Страница 48: ... 46 RS232 WIFI RS232 1 No D GND WIFI RS232 2 3 4 5 6 TX 7 12Vdc 8 1 2 3 4 5 6 7 8 9 RX 9 This RS232 port is used to connect the wifi datalogger ...

Страница 49: ... 47 1 Split Core Current Transformer CT dimension mm 2 Secondary output cable length is 4m 10 Appendix II Lead Outside ...

Страница 50: ...Add No 26 30 South Yongjiang Road Beilun 315806 Ningbo China Fax 86 0 574 8622 8852 Tel 86 0 574 8622 8957 E mail service deye com cn Web www deyeinverter com 30240301000690 Ver 2 2 2021 12 13 ...