- 34 -
5.8 Grid Setup Menu
For The Australian Market:
For compliance with AS/NZS 4777.2:2020 please select
from
• Australia A • Australia B • Australia C
• New Zealand
1/13
0/120/240
0/240/120
Grid Mode
Phase Type
Grid Level
IT system - neutral is not grounded
Grid Setting
Grid
Set1
Australia A
220V-3P
Grid Setting
Please contact your local grid operator for which option to select
Note: By selecting Australia A, Australia B or Australia C the power
quality response mode and grid protection settings will be reset to their
default values for Australia RegionA, B, C respectively.
Default volt-watt settings for different regions are shown in the following table:
Australia A
Australia B
Australia C
New Zealand
Voltage
253V
100%
253V
100%
242V
100%
250V
100%
260V
20%
260V
20%
250V
20%
260V
20%
215V
100%
215V
100%
224V
100%
215V
100%
207V
20%
207V
20%
216V
20%
195V
0%
Voltage
Voltage
Voltage
Inverter maximum active
power output level(P) % of S
rated
Inverter maximum active
power output level(P) % of S
rated
Inverter maximum active
power output level(P) % of S
rated
Inverter maximum active
power output level(P) % of S
rated
• INMETRO • EN50549-1
• EN50438 • IEC61727 • VDE_4105
• UTE_C15 • RD_1699 • CEI_0_21
• G98_G99
This menu is where you can select the country grid
parameters
.
For example: