KW
- 30-
5.6 Battery Setup Menu
Grid Signal:
Disable.
Grid Charge
Gen Charge
Grid Signal
Gen Signal
Gen Max Run Time
0.0 hours
Gen Down Time
0.5 hours
Battery Setting
Start
A
30%
30%
40A
40A
Batt
Set2
①
②
③
This is Battery Setup page.
Start =30%:
Percent S.O.C at 30% system will AutoStart a
connected generator to charge the battery bank.
A = 40A:
Charge rate of 40A from the attached
generator in Amps.
Gen Charge:
uses the gen input of the system to charge
battery bank from an attached generator.
Gen Signal:
Normally open relay that closes when the
Gen Start signal state is active.
Gen Max Run Time:
It indicates the longest time
Generator can run in one day, when time is up, the
Generator will be turned off. 24H means that it does
not shut down all the time.
Gen Down Time:
It indicates the delay time of the
Generator to shut down after it has reached the running
time.
①③
Start =30%:
No use
,
Just for customization.
A = 40A:
It indicates the Current that the
Grid charges the Battery.
Grid Charge:
It indicates that the grid charges
the battery.
This is Grid Charge, you need select.
②
Batt Mode
Lithium
Use Batt V
Battery Setting
Activate Battery
Max A Charge
Batt Capacity
Max A Discharge
40A
40A
400Ah
Batt
Mode
Use Batt %
No Batt
Battery capacity:
it tells Deye hybrid inverter to know
your battery bank size.
Use Batt V:
Use Battery Voltage for all the settings (V).
Use Batt %:
Use Battery SOC for all the settings (%).
Max. A charge/discharge:
Max battery charge/discharge
current(0-115A for 5KW model, 0-90A for 3.6KW model).
For AGM and Flooded, we recommend Ah battery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah battery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instructions.
No Batt:
tick this item if no battery is connected to the system.
Active battery:
This feature will help recover a battery that is over discharged by slowly charging from
the solar array or grid.
07/08/2021 11:11:10 Thu
76%
2.00
KW
-6.00
KW
0.00
KW
KW
0
15
0
12
0
12
0
12
ON
Signal
on
2.00
This page tells the PV and diesel generator
power the load and battery.
6
KW