Electronic Thermostat

Installation Guide

www.DEVI.com

Содержание devireg 532

Страница 1: ...DEVIreg 532 Electronic Thermostat Installation Guide www DEVI com...

Страница 2: ......

Страница 3: ...oom sensor to control the room tempera ture and an additional floor sensor to limit the maximum floor temperature It can be either flush mounted or sur face mounted The thermostat has a button for adj...

Страница 4: ...NTC 15kOhm at 25 C Sensing values 0 C 42 kOhm 25 C 15 kOhm 50 C 6 kOhm Hysteresis 0 4 C Ambient temperature 10 to 30 C Frost protection tempera ture 5 C Temperature range 5 35 C room temperature 20 5...

Страница 5: ...ilar use EN IEC 60730 1 general EN IEC 60730 2 9 thermostat 1 2 Safety Instructions Make sure the mains supply to the thermostat is turned off before installation IMPORTANT When the thermostat is used...

Страница 6: ...dered as live voltage Have this in mind if the sensor must be extended Always connect the thermostat to continuous power supply Do not expose the thermostat to moisture water dust and excessive heat 2...

Страница 7: ...s and doors Do not place the thermostat in a way that it will be exposed to direct sunlight Note A floor sensor enables a more accu rate temperature control and is recom mended in all floor heating ap...

Страница 8: ...or surface countersink the conduit if necessary Route the conduit to the connection box The bending radius of the conduit must be min 50mm Follow the steps below to mount the thermostat 1 Open the the...

Страница 9: ...the floor sensor in a conduit in the floor 3 Set the maximum floor temperature between 20 and 50 C by turning the screw with temperature indica tions in the upper left corner 4 Mount and reassemble t...

Страница 10: ...the floor sensor is placed The temperature of the bottom of a wooden floor can be up to 10 degrees higher than the top Floor manufactures often specify the max temperature on the top surface of the f...

Страница 11: ...05 8 mm HDF based laminate 800 kg m3 28 C 0 10 14 mm beech par quet 650 800 kg m3 31 C 0 13 22 mm solid oak plank 800 kg m3 32 C 0 17 Max carpet thick ness suitable for floor heating acc to EN 1307 34...

Страница 12: ...5 Disposal Instruction DEVIreg 532 12 Installation Guide...

Страница 13: ...DEVIreg 532 Installation Guide 13...

Страница 14: ...DEVIreg 532 14 Installation Guide...

Страница 15: ...inted material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes b...

Страница 16: ...40F1037 Thermostat Floor Room Sensor 220 240V 50 60Hz 5 to 35 C 15A 3450W 230V IP 31 Product Documentation DK EL 72 24 215 166 NO EL 5402662 FI SSTL 3531024 Designed in Denmark for Danfoss A S 5 7 0 3...