DISPERSION TUBE POSITIONING
Steam dispersion tubes:
the steam from the humidifier is injected in a duct or an air handling unit via a steam dispersion tube.
To obtain the best performance of the humidifier, select the longest pipe.
Absorption distance "D"
Make sure that the absorption distance is met in order to let the air absorb the steam dispersed by the
tubes. In this absorption distance, the steam is still visible in the air stream in the form of fog. If any
furniture is placed in this area, condensate may occur. For this reason, it is imperative to consider this
absorption distance when placing the humidifiers.
How to calculate absorption distance « D »
In order to determine the absorption distance, the attached calculation table can be used:
▪
RH1 = relative humidity of air before humidification in %.
▪
RH2 = relative humidity of air after humidification in %.
▪
D mini = minimum absorption distance in meters (m).
Inlet RH1 [%]
5
10
20
30
40
50
60
70
Outlet RH2 [%]
Minimum absorption distance "D" [m]
40
0,9 0,8
0,7
0,5
-
-
-
-
50
1,1 1
0,9
0,8
0,5
-
-
-
60
1,4 1,3
1,2
1
0,8
0,5
-
-
70
1,8 1,7
1,5
1,4
1,2
1
0,7
-
80
2,3 2,2
2,1
1,9
1,7
1,5
1,2
0,8
90
3,5 3,4
3,2
2,9
2,7
2,4
2,1
1,7
This calculation table is to be used for temperatures between 20°C and 25°C (68°F to 77°F) (Maximum
air speed 5 m/s). For calculated distances, contact your Devatec agent.
Spirit level
Fig.A 3-3.
Steam dispersion
tubes positioning
Содержание ElectroVap KIT MC 15
Страница 1: ...ElectroVap HUMIDIFIERS KIT MC Series Instruction Operation Manual ...
Страница 2: ...ELECTROVAP KIT MC 2 ...
Страница 31: ...ELECTROVAP KIT MC 31 3 8 3 WIRING DIAGRAMS KITMC 5 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 32: ...ELECTROVAP KIT MC 32 KITMC 8 à 20 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 33: ...ELECTROVAP KIT MC 33 KITMC 30 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 34: ...ELECTROVAP KIT MC 34 KITMC 40 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 35: ...ELECTROVAP KIT MC 35 KITMC 50 60 Up V 3x380 400 420 440 460 480 575 600Vac 50 60Hz ...
Страница 46: ...ELECTROVAP KIT MC 46 ...
Страница 47: ...ELECTROVAP KIT MC 47 ...