Customer Documentation DEV 5071
46
Copyright DEV Systemtechnik GmbH 2007-2017
5.5.4.2.5.8 .application.channelTable.channelEntry.channelOutCurrentSet
OID:
.1.3.6.1.4.1.21035.34.2.5.1.8
.x
Syntax:
INTEGER (0..80000)
Access:
read-write
Description:
The output current set point of the module in [mA].
Note:
The output current limit of each power supply module can be set
individually. However, it is recommended to keep the output current set
point for all installed modules at the same value.
Note the default setting and the limits for adjusting this value; please
refer to chapter 4.3.1.
5.5.4.2.5.9 .application.channelTable.channelEntry.channelOutCurrent
OID:
.1.3.6.1.4.1.21035.34.2.5.1.9
.x
Syntax:
INTEGER (0..60000)
Access:
read-only
Description:
The measured output current of the module in [mA]