29.4.11
UNIGATE fieldbus gateway for ProfibusDP V. 4.7
35
Deutschmann Automation GmbH & Co. KG
Hardware ports, switches and LEDs
11.4 Connectors
11.4.1
Connector to the external device (RS-interface)
The connection cable to the external device must be plugged in at the connector accessible on
the underside of the device.
Pin assignment (5-pin screw-type plug connector; not available for RS422)
Pin assignment (9-pin Sub-D, plug)
(Standard for the RS232/422-model, optional for the RS232/485-model)
Attention:
The assignment of the 9-pin Sub-D plug may differ from the above pin
assignment and also a customized configuration is possible.
Attention:
In case the RS-interface is NOT potentially divided, "GND" and "supply
0V" are connected internally.
Attention:
In case RS422 is selected, then the termination switch has to be set to
ON, in order to avoid communication errors!
Pin No.
Name
Function
1
10.8..30 V/DC power supply
Power supply
2
0 V power supply
Power supply
3
RX / RS485- (RS485 B)
Receive signal
4
TX / RS485+ (RS485 A)
Transmit signal
5
GND
Reference for PIN 3 + 4
Pin No.
Name
Function
1
2
Rx
Receive signal
RS485-
Transmit-receive signal
RS422- (Tx)
Transmit signal
3
Tx
Transmit signal
RS485+
Transmit-receive signal
RS422+ (Tx)
Receive signal
4
5
GND
Ground connection, reference for PIN 2+3+6+7
6
RS422- (Rx)
Receive signal
7
RS422+ (Rx)
Receive signal
8
9
Содержание UNIGATE RS232/422
Страница 2: ......