29.6.20
UNIGATE
®
Fieldbus Gateway UNIGATE
®
CL - MPI V. 3.1
53
Deutschmann Automation GmbH & Co. KG
Commissioning guide
16.6 Setting the MPI-address
Set the MPI-address at the fieldbus end of the module on the two rotary switches designated
"High" and "Low". This adjustment is carried out in a hexadecimal way.
Example:
The MPI-bus-ID is 26 decimal = 1A hexadecimal
The switch "High" has to be set to 1 and the switch "Low" has to be set to A.
Attention:
The MPI-bus must contain the set MPI-bus-address only once!
It is read in only on power-up of the Gateway!
16.7 MPI-bus-connection
Connect the device to the MPI-bus at the interface labelled "MPI".
16.8 Connection to the process device
Please also read the manual for the process device when commissioning the process device.
16.9 Connecting the supply voltage
Please connect 10..33 DC voltage to the terminals provided for this.
16.10 Shield connection
Earth the top-hat rail onto which the module has been snapped.
16.11 Literature
In order to help you quickly get to grips with the subject we recommend the book "Crashkurs S7
mit CD". The book can be ordered from the VDE Verlag (ISBN: 3-8007-2377-8).