INSTALLATION 

INSTRUCTIONS AND 

HOMEOWNER’S MANUAL

 

 

 
 
 
 
 
 
 

INSTALLER / SERVICE TECHNICIAN: 

Use the information in this manual for the installation / servicing and keep the document near the furnace for future reference.  

Communication wire connected between the indoor and outdoor units must be rated for at least 120VAC, they are protected by the 
outdoor unit breaker and must be sized appropriately. 

Do not install any metering device on the indoor coil. The expansion valve is located in the outdoor unit. If a metering device is 
already installed in the indoor coil, it must be removed. 

Both refrigerant lines must be separately insulated in order to avoid condensation and to ensure proper efficiency.  

 

COND-30 

COND-36 

Liquid line dia (In) 

1/4 

1/4 

Gas line dia (In) 

5/8 

5/8 

HOMEOWNER

Please keep this manual near the furnace for future reference. 

CAUTION 

DO NOT TAMPER WITH THE UNIT OR ITS CONTROLS. CALL A QUALIFIED SERVICE TECHNICIAN. 
THE  WELDS  MUST  BE  DONE  BY  USING  NITROGEN  PROTECTIVE  GAS.  NON-COMPLIANCE  WILL  MEAN  THE  IMMEDIATE 
CANCELLATION OF THE WARRANTY. 
 

Manufactured by : 

Dettson Industries Inc. 

Sherbrooke (Quebec) Canada  

http://www.dettson.ca/

 

 

 

 

 

COND-30

 

COND-36

 

ALIZÉ MODELS

 

Содержание COND-30

Страница 1: ...ocated in the outdoor unit If a metering device is already installed in the indoor coil it must be removed Both refrigerant lines must be separately insulated in order to avoid condensation and to ens...

Страница 2: ...on the interface card should be blinking once every two seconds 3 The communicating thermostat will display Heat Pump Found 4 Set the thermostat to COOL mode and adjust the set point to a lower value...

Страница 3: ...20 6 10 1 Electrical wiring 20 6 10 2 Air purging and leakage test 20 6 10 3 Outdoor unit condensate drainage 20 6 10 4 Check after installation and test operation 21 6 10 5 Operation test 21 7 TROUBL...

Страница 4: ...Figure 12 Multiposition configurations 17 Figure 13 Splashguard without front slope 17 Figure 14 Splashguard with front slope 18 Figure 15 Multiposition field conversion 18 Figure 16 Condensate drain...

Страница 5: ...uately grounded in accordance with the local electric codes Have all wiring connected tightly Loose connections may lead to overheating and a possible fire hazard All installation or repair work shall...

Страница 6: ...onnection pipe gas additional charge Refrigerant charge Connection pipe length Electronic expansion valve Aluminum fins copper tube Axial flow Automatic defrosting R410A Rotary COP SEER 1 Model EER De...

Страница 7: ...7 1 4 OPERATION CHARACTERISTICS CURVES Figure 1 Operation characteristic curves 30K Figure 2 Operation characteristic curves 36K...

Страница 8: ...8 1 5 CAPACITY VARIATION RATIO ACCORDING TO TEMPERATURE Figure 3 30K Capacity ratio vs outdoor temperature Figure 4 36K Capacity ratio vs outdoor temperature...

Страница 9: ...9 1 6 NOISE CRITERIA CURVE TABLES Figure 5 30K Noise curve Figure 6 36K noise curve Compressor frequency Hz Compressor frequency Hz...

Страница 10: ...Figure 7 30 36K dimensions 3 REFRIGERANT SYSTEM DIAGRAM Figure 8 refrigerant system diagram Properly insulate ALL refrigerant tubing from outdoor units to the interior cooling coil to prevent water d...

Страница 11: ...11 4 SCHEMATIC DIAGRAMS 4 1 ELECTRICAL DIAGRAM Figure 9 30 36K Electrical diagram...

Страница 12: ...12 4 2 PRINTED CIRCUIT BOARD Figure 10 30 36K Circuit board...

Страница 13: ...tpump heat only 5 2 FUNCTION CONTROL 5 2 1 Temperature Parameters Indoor thermostat temperature Indoor ambient temperature Note T is determined by indoor and outdoor units If the indoor unit controls...

Страница 14: ...will run at reduced frequency d If 7 62 2 144 the compressor will stop and the indoor fan will run at pre set speed 2 Heating overload a If 7 52 2 126 the unit will return to n its original operation...

Страница 15: ...unit is installed in accordance with the installation instructions and is convenient for maintenance and repair 6 The maximum height difference between the indoor cooling coil and the outdoor unit is...

Страница 16: ...lled with a vertical and horizontal drain pans and can be configured for upflow downflow horizontal blow through or horizontal pull through installations In the center opening of vertical drain pan a...

Страница 17: ...17 Figure 12 Multiposition configurations Figure 13 Splashguard without front slope...

Страница 18: ...out holes in the front panel to prevent air leakage Figure 15 Multiposition field conversion 6 7 3 Condensate drain Coils are equipped with multiple drain connections Determine the drain connections...

Страница 19: ...r proper connections Note that the performance of the outdoor unit will be affected and will not modulate QUICK SETUP Erreur Source du renvoi introuvable Figure 17 Chinook gas furnace Figure 18 Suprem...

Страница 20: ...charging hose of manifold valve to charge end of low pressure valve both high low must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open the handle of Lo manifold valve 4 Op...

Страница 21: ...ctly and securely It may cause electric malfunction or damage parts Has the unit been securely earthed It may cause electrical leakage Is the inlet or outlet blocked It may cause insufficient cooling...

Страница 22: ...22 7 TROUBLESHOOTING...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...25...

Страница 26: ...irectly touching any of the circuit parts without first turning OFF the power NOTE A large capacity electrolytic capacitor is used in the outdoor unit controller inverter Therefore if the power supply...

Страница 27: ...ing properly with the communicating furnace this LED should be blinking by short bursts Normal with communicating installations If the LED is ON most of the time and the it turns OFF for very short pe...

Страница 28: ...ction Blinks 14 times The PFC circuit over current Stop for ID and OD doesn t match Blinks 16 times The indoor unit and outdoor unit doesn t match Compressor frequency limit by over current protection...

Страница 29: ...29...

Страница 30: ...load protection Possible reasons insufficient or too much refrigerant blockage of capillary and decrease of suction temp improper running of compressor burning in or stuck of bearing damage of discha...

Страница 31: ...unit AP1 below refers to the outdoor control panel USUAL SYMPTOMS Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC 240VAC If the inductor L well c...

Страница 32: ...sequence correct Is the voltage input in the normal range test the voltage between L N of wiring board XT by DC voltage meter Is the coil resistance of compressor normal Is the compressor coil insulat...

Страница 33: ...protection USUAL SYMPTOMS Is the outdoor ambient temperature in a normal range Is the indoor and outdoor fans are running normal How is the radiating environment of the indoor and outdoor unit AP1 BEL...

Страница 34: ...tart up malfunction USUAL SYMPTOMS Is the compressor wiring correct Is the stop time of the compressor enough Is the compressor damaged Is the refrigerant charged too much AP1 BELOW IS THE CONTROL BOA...

Страница 35: ...35 7 6 4 Out of step diagnosis for the compressor USUAL SYMPTOMS Is the pressure to high Is the input voltage to low AP1 BELOW IS THE CONTROL BOARD OF OUTDOOR UNIT...

Страница 36: ...harge malfunction USUAL SYMPTOMS Is the electronic expansion valve connected correctly Is the expansion valve damaged Is the refrigerant leaking Is the overload protector damaged AP1 BELOW IS THE CONT...

Страница 37: ...37 7 6 6 PFC correction for power factor malfunction AP1 BELOW IS THE CONTROL BOARD OF OUTDOOR UNIT Check if the inductor L of outdoor unit and PFC capacity are damaged...

Страница 38: ...ire and the built in wiring of the indoor and the outdoor are connected correctly and not damaged Is the communication circuit of the indoor mainboard is damaged Is the communication circuit of the ou...

Страница 39: ...39 7 6 8 Flow chart outdoor communication circuit detecting...

Страница 40: ...40 7 6 9 High pressure protection...

Страница 41: ...PROCEDURE OF OUTDOOR UNIT WARNING Be sure to wait for a minimum of 10 minutes after turning off all power supplier before disassembly NOTE Electric heater band is not shown below Models COND 30 01 ET...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 9 COMPONENTS AND REPLACEMENT PARTS 9 1 EXPLODED VUE 30 36K...

Страница 49: ...4300876703 1 21 Temperature sensor COND 3900031001 COND 3900031001 1 22 Rear grill COND 01475013 COND 01163491 1 23 Condenser assy COND 01163509 COND 01163509 1 24 Clapboard COND 01233134 COND 012331...

Страница 50: ...7 75 2 94 237 114 0 904 28 2 72 41 99 37 12 169 76 2 844 239 115 0 88 30 1 68 79 100 38 11 52 171 77 2 752 241 116 0 856 32 0 65 37 102 39 11 06 172 78 2 663 243 117 0 833 34 1 62 13 104 40 10 62 174...

Страница 51: ...75 2 206 237 114 0 678 28 2 54 31 99 37 9 003 169 76 2 133 239 115 0 66 30 1 51 59 100 38 8 642 171 77 2 064 241 116 0 642 32 0 49 02 102 39 8 297 172 78 1 997 243 117 0 625 34 1 46 6 104 40 7 967 17...

Страница 52: ...9 79 26 47 08 149 65 10 18 219 104 2 955 10 12 306 2 81 27 45 07 151 66 9 827 221 105 2 872 12 11 289 6 82 28 43 16 153 67 9 489 223 106 2 792 14 10 274 84 29 41 34 154 68 9 165 225 107 2 715 16 9 259...

Страница 53: ...orized Installation of Accessory Equipment Dettson Industries Inc authorizes the application of accessory equipment which will operate in conjunction with its products provided that the following cond...

Отзывы: