background image

WARNING

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for
each appliance connected to the venting system
being placed into operation could result in carbon
monoxide poisoning or death. The following steps
shall be followed for each appliance connected to
the venting system being placed into operation,
while all other appliances connected to the
venting system are not in operation:

1. Seal

any

unused

openings

in

venting

system;

2. Inspect

the

venting

system

for

proper

size

and

horizontal

pitch,

as

required

in the National Fuel Gas Code,

ANSI

Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code, CSA B149.1 and
these instructions.

Determine that there

is no blockage or restriction,

leakage,

corrosion and other deficiencies which could
cause an unsafe condition;

3. As far as practical, close all building doors

and windows and all doors between the
space in which the appliance(s) connected
to the venting system are located and other
spaces of the building;

4. Close fireplace dampers;
5. Turn on clothes dryers and any appliance not

connected to the venting system. Turn on
any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer
exhaust fan;

6. Follow the lighting instructions. Place the

appliance being inspected into operation.
Adjust

the

thermostat

so

appliance

is

operating continuously;

7. Test for spillage from draft hood equipped

appliances at the draft hood relief opening
after 5 minutes of main burner operation.
Use the flame of a match or candle;

8. If improper venting is observed during any

of the above tests, the venting system must
be corrected in accordance with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or
Natural Gas and Propane Installation code,
CSA B149.1;

9. After it has been determined that each

appliance connected to the venting system
properly vents when tested as outlined
above,

return doors,

windows,

exhaust

fans, fireplace dampers and any other gas-
fired burning appliance to their previous
conditions of use;

1.4

DETECTION SYSTEMS

It is recommended that carbon monoxide detectors be
installed wherever oil or gas fired heaters are used.
Carbon monoxide can cause bodily harm or death.
For this reason, agency approved carbon monoxide
detectors should be installed in your residence and
properly maintained to warn of dangerously high carbon
monoxide levels.
Also, the house should be equipped with approved and
properly maintained fire extinguishers.
Your unit is equipped with safety devices that can prevent
it from functioning when anomalies are detected such as
a blocked venting system.

1.5

DANGER OF FREEZING

CAUTION

FROZEN AND BURST WATER PIPE HAZARD
Failure to protect against the risk of freezing may
result in property damage. Special precautions
MUST be made if installing furnace in an area
which may drop below freezing. This can cause
improper operation or damage to equipment. If
furnace environment has the potential of freezing,
the drain trap and drain line must be protected.

CAUTION

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in
burst water pipes and/or property damage.

If

a condensate pump is installed,

a clogged

condensate drain or a failed pump may cause
the furnace to shut down.

Do not leave the

home unattended during freezing weather without
turning off water supply and draining water pipes
or otherwise protecting against the risk of frozen
pipes.
Ensure all condensate drain connections are
secured and liquid tight. Use the furnished tube
clamps and verify tightness

6

Содержание CC15-M-V

Страница 1: ...future reference Caution Do not tamper with the unit or its controls Call a qualified service technician HOMEOWNER Please keep this manual near the furnace for future reference Manufactured by Dettson...

Страница 2: ...1 NON COMMUNICATING MODULATING ONE STAGE OR TWO STAGE THERMOSTAT 16 7 3 2 THERMOSTAT INPUT 16 7 4 ALTERNATE POWER SUPPLY 17 8 VENTING AND COMBUSTION AIR PIPING 19 8 1 GENERAL 19 8 2 DIRECT VENT 19 8 3...

Страница 3: ...Alternate horizontal termination A 22 Figure 23 Alternate horizontal termination B 22 Figure 24 Alternate horizontal termination C 22 Figure 25 Direct vent clearance 23 Figure 26 Other than Direct ve...

Страница 4: ...assess the damage and to replace all critical parts that were in contact with water 3 Do not store gasoline or any other flammable substances such as paper or carton near the furnace 4 Do not stack it...

Страница 5: ...o be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace See section 5 DUCT INSTALLATION This furnace may be installed with a two pipe sealed combus...

Страница 6: ...th the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or Natural Gas and Propane Installation code CSA B149 1 9 After it has been determined that each appliance connected to the venting system properl...

Страница 7: ...n Code NSCNGPIC CAN CSA B149 1 General installation NFGC and the NFPA 90B For copies contact the National Fire Protection Association Inc Battery march Park Quincy MA 02269 or for only the NFGC contac...

Страница 8: ...in this manual The furnace should be located as close to the chimney vertical venting or to the outside vent wall horizontal venting as possible 2 3 1 Location relative to cooling equipement The cooli...

Страница 9: ...on Figure 3 Dimensions Figure 4 Top view Figure 5 Drain Trap Localisation Figure 6 Pressure switch connections for multipositions 4 1 UPFLOW The condensate trap must be outside the furnace casing Use...

Страница 10: ...gths 1 4 5 and 2 9 25 3 Remove the appropriate knock out for drain trap Refer to Figure 5 for the location of the drain trap in downflow configuration 4 Cut open the pressure port located on the conde...

Страница 11: ...er to ensure proper drainage of the condensate See figure 12 4 3 1 Horizontal Condensate drain connection 1 Remove PVC tubes from the ID blower condensate box and vent collector and block the openings...

Страница 12: ...ith local building codes 12 The venting must be drained using a PVC 636 tee Connect this tee to a P trap and connect it to your condensate drain Commercially available condensate trap exist for use wi...

Страница 13: ...fasteners for type of ductwork used Seal supply and return duct connections to the furnace with code approved tape or duct sealer Ductwork passing through an unconditioned space should be insulated t...

Страница 14: ...ot have a 90 degree elbow and 10 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in...

Страница 15: ...ert the gas valve to propane 1 Move the switch located on the valve to the off position 2 Remove the NAT GAS label from the top of the gas valve 3 Using a pair of tweezers or needle nose pliers place...

Страница 16: ...mum mode of operation and will give the best temperature control with minimal temperature variation from the desired set point Operation with a 2 stage thermostat will proceed as follow call on W1 wil...

Страница 17: ...te Power from an alternate power supply that is non sinusoidal may damage the furnace electronics or cause erratic operation Contact the alternate power supply manufacturer for specifications and deta...

Страница 18: ...Figure 17 Wiring Diagram 18...

Страница 19: ...rrent edition of the National Fuel Gas Code and the vent or liner manufacturer s installation instructions Care must be taken to prevent the exhaust gases from one appliance from contaminating the com...

Страница 20: ...e 2 Count the number of elbows for each pipe 3 For each pipe multiply the number of elbows by the equivalent length for the type of elbow used see table 11 Record the equivalent length of all the elbo...

Страница 21: ...INATION All clearance specified in this manual are in accordance with the current CSA B149 1 Natural and Propane Installation Code and the current ANSI Z223 1 NFPA 54 National Fuel Gas Code For cleara...

Страница 22: ...r the elbows to fit on the pipes Holes in the roof for two pipe terminations should be spaced no more than 18 457 mm apart Termination elbows will be installed after the vent and combustion air pipe a...

Страница 23: ...Figure 25 Direct vent clearance 23...

Страница 24: ...Figure 26 Other than Direct vent clearance 24...

Страница 25: ...ve the burner compartment control access door 3 IMPORTANT Be sure that the manual gas control has been in the OFF position for at least five minutes Do not attempt to manually light the main burners 4...

Страница 26: ...oth pressure switches quickly Once both pressure switches are sensed to be closed the inducer will run for 25 seconds before the ignition trial starts Hot surface igniter is energized during the pre p...

Страница 27: ...esent the furnace will not operate in any mode and a fault will be displayed 9 12 REPLACING FURNACE CONTROL In the event that the furnace control must be replaced the memory card must be detached from...

Страница 28: ...r future reference To keep your operating costs low and to eliminate unnecessary service calls we have provided a few guidelines These guidelines will help you understand how your gas furnace operates...

Страница 29: ...g 3 Leave the building immediately 4 Immediately call your gas supplier Follow the gas supplier s instructions 5 If you cannot reach the gas supplier call the fire department 10 2 OPERATING YOUR FURNA...

Страница 30: ...sense current is weak or weird 1 Clean or replace de flame sensor 2 Check gas outlet pressure 3 Take a combustion analysis A dirty flamme sensor needs to be investigate 13 Flame lost 1 Clean or replac...

Страница 31: ...e gas valve will immediately close flame will be lost blower motor operation will immediately stop and the furnace will shut down normally with Inducer post purge at the correct speed After the post p...

Страница 32: ...Outlet gas pressure high fire 100 Outlet gas pressure low fire 40 Static pressure in return Static pressure in supply Temperature rise Is drain trap filled with water Is drain trap outlet vented with...

Страница 33: ...Table 18 Specification table 1 Maximum CFM acheived in standard duct systems 2 Maximum CFM acheived using SmartDuct system 33...

Страница 34: ...12 PART LIST Figure 27 Exploded view...

Страница 35: ...Figure 28 Exploded view continued...

Страница 36: ...Table 19 Part list Chinook Compact...

Страница 37: ...Table 20 Part list continued...

Страница 38: ...13 NOTES 38...

Страница 39: ...39...

Страница 40: ...40...

Отзывы: