Det-Tronics W867 Скачать руководство пользователя страница 1

APPLICATION

The Det-Tronics W867 Ultraviolet/Infrared (UV/IR) Test
Lamp is a portable, battery operated source of
ultraviolet and infrared radiation that can be used for
periodic inspection of UV, single frequency IR and
UV/IR flame detection systems.  It produces UV and IR
radiation to verify response of the flame detection
system without the need for an open flame, and is
suitable for use in hazardous (classified) areas.  (Note:
Det-Tronics Dual Frequency IR detectors require the
model W868 Dual Frequency IR Test Lamp for testing.)

SPECIFICATIONS

ENCLOSURE—

Cast aluminum.

CERTIFICATION—

Class I, Division 1, Groups C and D;
Class II, Division 1, Groups E, F and G.
For storage and use in dr y or damp
locations only.

ELECTRICAL RATINGS—

Battery Charger Input Voltage:

120 volts ac, 60 Hz
220 volts ac, 50 Hz 
(optional).

TEMPERATURE RANGE—

Operating: +5°F to +122°F (–15°C to +50°C).
Charge:  

+32°F to +104°F (0°C to +40°C).

Storage:  

+5°F to +104°F (–15°C to +40°C).

OPERATING TIME—

Approximately 15 minutes continuous between
recharges.  This will vary with the ambient temperature.

OUTPUT—

Broadband emissions in both UV and IR spectra.

APPROXIMATE OPERATING RANGE—

UV detector (25 cps sensitivity setting):  

>50 feet (15 meters).

IR detector (40 cps sensitivity setting):  

5 feet (1.5 meters).

UV/IR detector (16 cps sensitivity setting):  

5 feet (1.5 meters).

DIMENSIONS—

See Figure 1.

WEIGHT (APPROXIMATE)—

14 pounds (6.2 kilograms).

INSTRUCTIONS

Ultraviolet/Infrared Test Lamp

W867

©

Detector Electronics Corporation 2001

7/01

95-8309-04

DET

-

TRONICS

®

F M

APPROVED

Содержание W867

Страница 1: ... E F and G For storage and use in dry or damp locations only ELECTRICAL RATINGS Battery Charger Input Voltage 120 volts ac 60 Hz 220 volts ac 50 Hz optional TEMPERATURE RANGE Operating 5 F to 122 F 15 C to 50 C Charge 32 F to 104 F 0 C to 40 C Storage 5 F to 104 F 15 C to 40 C OPERATING TIME Approximately 15 minutes continuous between recharges This will vary with the ambient temperature OUTPUT Br...

Страница 2: ...structions for further information CAUTION Do not remove the shock insulators from the lens cap or battery storage compartment SYSTEM CHECKOUT A system checkout should be performed after installation is complete A periodic maintenance checkout with minimum frequency of once every six months should be scheduled to ensure that the system is in proper operating condition Depending on the degree of ha...

Страница 3: ...ction Plug the charger cable plug into the battery Plug the battery charger into the appropriate ac outlet The Power On and Fast Charge LEDs on the battery charger should be on When the battery is fully charged the Fast Charge LED will go out This should take from 12 to 14 hours from a discharged state To return the W867 Test Lamp to service unplug the battery charger from the ac outlet Disconnect...

Страница 4: ...E G I STERED F I R M R E G I S TERED F I R M Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 Operator 952 941 5665 or 800 765 FIRE Customer Service 952 946 6491 Fax 952 829 8750 www detronics com E mail detronics detronics com ...

Отзывы: